Carrier 30XA080-500 Fan User Manual


 
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300026-01 Printed in U.S.A. Form 30XA-10SI Pg 1 11-09 Replaces: 30XA-5SI
Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-78
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 1
Step 2 — Place, Mount and Rig Unit. . . . . . . . . . . . . 2
•PLACING UNIT
MOUNTING UNIT
RIGGING UNIT
Step 3 — Cooler Fluid and Drain Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
GENERAL
UNITS WITH A HYDRONIC PUMP PACKAGE
UNITS WITHOUT A HYDRONIC PUMP PACKAGE
DUAL CHILLER CONTROL
COOLER PUMP CONTROL
BRINE UNITS
PREPARATION FOR YEAR-ROUND OPERATION
Step 4 — Fill the Chilled Water Loop . . . . . . . . . . . . 56
WATER SYSTEM CLEANING
WATER TREATMENT
SYSTEM PRESSURIZATION
FILLING THE SYSTEM
SET WATER FLOW RATE
PUMP MODIFICATION/TRIMMING
FREEZE PROTECTION
PREPARATION FOR WINTER SHUTDOWN
Step 5 — Make Electrical Connections . . . . . . . . . . 62
POWER SUPPLY
FIELD POWER CONNECTIONS
•POWER WIRING
FIELD CONTROL POWER CONNECTIONS
CARRIER COMFORT NETWORK®
COMMUNICATION BUS WIRING
NON-CCN COMMUNICATION WIRING
FIELD CONTROL OPTION WIRING
DUAL CHILLER LEAVING WATER SENSOR
Step 6 — Install Accessories . . . . . . . . . . . . . . . . . . . . 77
ENERGY MANAGEMENT MODULE
REMOTE ENHANCED DISPLAY
LOW AMBIENT TEMPERATURE OPERATION
MINIMUM LOAD ACCESSORY
UNIT SECURITY/PROTECTION ACCESSORIES
COMMUNICATION ACCESSORIES
SERVICE OPTIONS
CONTROL TRANSFORMER
Step 7 — Leak Test Unit . . . . . . . . . . . . . . . . . . . . . . . . . 77
Step 8 — Refrigerant Charging. . . . . . . . . . . . . . . . . . 77
DEHYDRATION
REFRIGERANT CHARGE
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location. Only trained, qualified installers and service
mechanics should install, start up, and service this equipment.
When working on the equipment, observe precautions in the
literature, and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes.
Wear safety glasses and work gloves.
Use care in handling, rigging, and setting bulky equipment.
INTRODUCTION
These instructions cover installation of 30XA080-500 air-
cooled liquid chillers with electronic controls and units with
factory-installed options (FIOPs). See Fig. 1.
INSTALLATION
Storage —
If the unit is to be stored for a period of time be-
fore installation or start-up, be sure to protect the machine
from construction dirt. Keep protective shipping covers in
place until the machine is ready for installation.
Step 1 — Inspect Shipment — Inspect unit for dam-
age upon arrival. If damage is found, immediately file a claim
with the shipping company, and contact your local Carrier
representative.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
IMPORTANT: This equipment generates, uses, and
can radiate radio frequency energy and if not installed
and used in accordance with these instructions may
cause radio interference. It has been tested and found
to comply with the limits of a Class A computing
device as defined by FCC (Federal Communications
Commission, U.S.A.) regulations, Subpart J of Part 15,
which are designed to provide reasonable protection
against such interference when operated in a commer-
cial environment.
AQUAFORCE
®
30XA080-500
Air-Cooled Liquid Chillers