At installation altitudes from 2000 to 4500 ft, this furnace must be derated 5 percent by an authorized Gas Conversion Station or Dealer. To
determine correct input rate for altitude, see example above and use 0.95 as derate multiplier factor.
b. Reinstall burner box cover.
NOTE: Clocking gas input rate MUST always be performed with the burner box cover INSTALLED.
c. Check that gas valve adjustment caps are in place for proper input to be clocked.
d. Obtain yearly heat value average for local gas supply.
NOTE: Be sure heating value of gas used for calculations is correct for your altitude. Consult local gas utility for altitude adjustment of gas heating
value.
e. Check and verify orifice size in furnace. NEVER ASSUME THE ORIFICE SIZE. ALWAYS CHECK AND VERIFY.
f. Turn off all other gas appliances and pilots.
g. Move setup switch SW-2 to ON position. (See Fig. 31.) This keeps furnace locked in low-heat operation.
h. Jumper R to W/W1.
i. Let furnace run for 3 minutes in low-heat operation.
j. Measure time (in sec) for gas meter to complete 1 revolution. Note reading.
k. Refer to Table 15 for cubic ft of gas per hr.
l. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
Table 13—Model 355MAV Orifice Size and Manifold Pressure for Correct Input (Continued)
(Tabulated Data Based on 20,000 Btuh High Heat/13,000 Btuh Low Heat per Burner, Derated 2 Percent for Each 1000 ft Above
Sea Level)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64 0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A. Only
7001
to
8000
625 43 3.8/1.6 42 3.3/1.4 42 3.4/1.4 42 3.5/1.5 42 3.6/1.5
650 43 3.5/1.5 43 3.7/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
675 44 3.8/1.6 43 3.4/1.4 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6
700 44 3.5/1.5 44 3.6/1.5 44 3.8/1.6 43 3.4/1.4 43 3.5/1.5
725 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5 44 3.7/1.6
750 45 3.7/1.6 45 3.8/1.6 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5
775 45 3.5/1.5 45 3.6/1.5 45 3.7/1.6 45 3.8/1.6 44 3.3/1.4
800 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 45 3.7/1.6
825 47 3.6/1.5 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5
850 47 3.4/1.4 47 3.5/1.5 47 3.7/1.5 45 3.2/1.3 45 3.3/1.4
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64 0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A. Only
Altitudes
8001
to
9000
600 43 3.8/1.6 42 3.3/1.4 42 3.4/1.4 42 3.5/1.5 42 3.6/1.5
625 43 3.5/1.5 43 3.6/1.5 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
650 44 3.7/1.6 43 3.4/1.4 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6
675 44 3.5/1.5 44 3.6/1.5 44 3.7/1.6 44 3.8/1.6 43 3.4/1.5
700 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 44 3.6/1.5 44 3.7/1.6
725 45 3.6/1.5 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.4
750 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 45 3.8/1.6 44 3.2/1.4
775 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5
800 47 3.6/1.5 47 3.7/1.6 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64 0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A. Only
9001
to
10,000
575 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4 42 3.5/1.5 42 3.6/1.5
600 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6 42 3.2/1.3 42 3.3/1.4
625 44 3.7/1.6 44 3.8/1.6 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6
650 44 3.4/1.4 44 3.5/1.5 44 3.7/1.5 44 3.8/1.6 43 3.4/1.4
675 44 3.8/1.6 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5
700 45 3.6/1.5 45 3.7/1.6 45 3.8/1.6 44 3.3/1.4 44 3.4/1.4
725 45 3.3/1.4 45 3.4/1.5 45 3.6/1.5 45 3.7/1.6 45 3.8/1.6
750 47 3.7/1.6 45 3.2/1.4 45 3.3/1.4 45 3.4/1.5 45 3.5/1.5
775 47 3.5/1.5 47 3.6/1.5 47 3.7/1.6 45 3.2/1.4 45 3.3/1.4
*Orifice numbers 45 are factory installed.
—54—