j. Remove jumpers R to W/W1 and R to W2.
3. Verify natural gas input rate by clocking gas meter.
NOTE: Be sure all pressure tubing, combustion-air and vent pipes, and burner enclosure front are in place when checking input by clocking gas
meter.
a. Calculate high-altitude adjustment (if required).
CAUTION: DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes, etc.) can cause excessive burner noise
and misdirection of burner flames. This can result in flame impingement of burners and heat exchangers, causing failures.
(See Fig. 57.)
UNITED STATES
At altitudes above 2000 ft, this furnace has been approved for a 2 percent derate for each 1000 ft above sea level. See Example and Table 14 for
derate multiplier factor.
Table 13—Model 355MAV Orifice Size and Manifold Pressure for Correct Input (Continued)
(Tabulated Data Based on 20,000 Btuh High Heat/13,000 Btuh Low Heat per Burner, Derated 2 Percent for Each 1000 ft Above
Sea Level)
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64 0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A. and Canada
4001
to
5000
725 43 3.7/1.5 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4 42 3.4/1.4
750 44 3.4/1.4 43 3.5/1.5 43 3.7/1.5 43 3.8/1.6 42 3.2/1.4
775 44 3.7/1.6 44 3.8/1.6 43 3.4/1.4 43 3.5/1.5 43 3.7/1.5
800 44 3.5/1.5 44 3.6/1.5 44 3.7/1.6 44 3.8/1.6 43 3.4/1.4
825 44 3.2/1.4 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5 44 3.7/1.6
850 45 3.7/1.6 45 3.8/1.6 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5
875 45 3.5/1.5 45 3.6/1.5 45 3.7/1.6 44 3.2/1.3 44 3.3/1.4
900 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 45 3.8/1.6
925 47 3.7/1.6 45 3.2/1.4 45 3.3/1.4 45 3.4/1.5 45 3.6/1.5
950 47 3.5/1.5 47 3.6/1.5 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64 0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A. and Canada
5001
to
6000
700 43 3.6/1.5 43 3.7/1.6 42 3.2/1.3 42 3.3/1.4 42 3.4/1.4
725 43 3.4/1.4 43 3.5/1.5 43 3.6/1.5 43 3.7/1.6 43 3.8/1.6
750 44 3.6/1.5 44 3.7/1.6 43 3.4/1.4 43 3.5/1.5 43 3.6/1.5
775 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5 44 3.7/1.6 43 3.4/1.4
800 44 3.2/1.3 44 3.3/1.4 44 3.4/1.4 44 3.5/1.5 44 3.6/1.5
825 45 3.6/1.5 45 3.7/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.4
850 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5 45 3.8/1.6 44 3.2/1.4
875 45 3.2/1.4 45 3.3/1.4 45 3.4/1.5 45 3.6/1.5 45 3.7/1.5
900 47 3.6/1.5 47 3.7/1.6 45 3.3/1.4 45 3.4/1.4 45 3.5/1.5
925 47 3.4/1.4 47 3.5/1.5 47 3.7/1.5 45 3.2/1.3 45 3.3/1.4
950 48 3.7/1.6 48 3.8/1.6 47 3.5/1.5 47 3.6/1.5 47 3.7/1.6
975 48 3.5/1.5 48 3.6/1.5 48 3.8/1.6 47 3.4/1.4 47 3.5/1.5
1000 48 3.3/1.4 48 3.5/1.5 48 3.6/1.5 48 3.7/1.6 48 3.8/1.6
ALTITUDE
RANGE
(FT)
AVG GAS
HEAT VALUE
(BTU/CU FT)
SPECIFIC GRAVITY OF NATURAL GAS
0.58 0.60 0.62 0.64 0.66
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
Orifice
no.
Manifold
Pressure
U.S.A. Only
6001
to
7000
650 42 3.2/1.3 42 3.3/1.4 42 3.4/1.4 42 3.5/1.5 42 3.6/1.5
675 43 3.6/1.5 43 3.7/1.6 43 3.8/1.6 42 3.2/1.4 42 3.3/1.4
700 44 3.8/1.6 43 3.4/1.5 43 3.6/1.5 43 3.7/1.6 43 3.8/1.6
725 44 3.6/1.5 44 3.7/1.6 44 3.8/1.6 43 3.4/1.4 43 3.5/1.5
750 44 3.3/1.4 44 3.4/1.5 44 3.6/1.5 44 3.7/1.6 44 3.8/1.6
775 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4 44 3.4/1.5 44 3.5/1.5
800 45 3.5/1.5 45 3.7/1.5 45 3.8/1.6 44 3.2/1.4 44 3.3/1.4
825 45 3.3/1.4 45 3.4/1.5 45 3.6/1.5 45 3.7/1.6 45 3.8/1.6
850 47 3.7/1.6 45 3.2/1.4 45 3.4/1.4 45 3.5/1.5 45 3.6/1.5
875 47 3.5/1.5 47 3.6/1.5 45 3.2/1.3 45 3.3/1.4 45 3.4/1.4
* Orifice numbers 45 are factory installed.