Balcar R410A Air Conditioner User Manual


 
165
INSTALLATION MANUAL
85464359426000 (EN)
To Personnel Charged in Installation Work and Service
Remote Controller Wireless Kit
MODEL : TCB-AX21U (W)-E
How to install the sensors
*
The positions where the sensors can be installed are limited to the
corners (A) in Fig. 1. Therefore, for installation of the sensor units,
consider the direction when a panel is installed to the indoor unit.
1. Remove the suction grille.
2. Take off the screw fixing the corner cap and remove the corner cap
sliding it side-ward. (Fig. 2)
Fig. 1
Fig. 2
3. The thermal insulation material is stuffed in the square hole
provided to pass through cables of the panel, so take off it once
and pass the cable out of the sensor of wireless remote controller
through the grille. Using a clamp, fix the cable with screws and
then be sure to stuff again the removed thermal insulation material
as original. (Fig. 3)
If the thermal insulation material is not stuffed, dewing may
happen.
Fig. 3
4. After cabling according to How to perform cabling of sensor units,
remain the cable length enough to remove the sensor unit and fix it
with screws using a clamp. (Fig. 3)
5. Install the sensor units to the panel. In this time, slide the panel so
that the hooks are fit in completely at 3 positions.
And also be careful not to pinch the cable. (Fig. 4)
Fig. 4
NOTES :
1. Avoid to twist the cables of the operation section with cables of the
power supply, etc. It causes a malfunction.
2. When noise is contained to the power supply of the indoor unit,
counter measures such as mounting the noise filter is necessary.
How to perform cabling of sensor units
Connection diagram
To operate a group control of multiple indoor units by 2 remote
controllers
*
Master and Sub remote controllers are operable even if they are
installed to any indoor unit.
(Total cable length: Within 200m)
How to set the room temperature sensor
The room temperature sensors are equipped in the indoor unit and
the wireless remote controller. One of two sensors works.
The room temperature sensor is set to the indoor unit side at the
shipment from the factory. To select the sensor in the remote
controller, push the SENSOR button (Right figure) inside of the
remote controller cover and check Main sensor disappears from
LCD.
How to set the address switch
When the multiple sensors are installed in the same room, an
address can be set to prevent cross communication.
When replacing the battery and pushing SET button, the address of
the remote controller becomes [ALL] and the sensor is enabled to
receive signal regardless of setting of address switch of the
operation section.
For selecting of the remote controller address, refer to Owners
Manual.
Change the address of the sensor by removing screws of P.C. board
cover of the sensor unit. After then, fix the cover with screws using
a clamp.
Slide switch
Check the slide switch in the battery box of the remote controller is
set to [S] / [A] at shipment from the factory.
Do not change the setting.
Test run
How to use [TEST]
1. Turn No.1 of DIP switch [S003] on sensor P.C. board from OFF to
ON.
2. During the test run, all the indication lamps on LCD flash.
3. During the test run, the temperature cannot be controlled.
4. After the test run, be
sure to turn DIP switch 1
from ON to OFF and
check the indication
lamps do not flash.
Use [TEST] function
only for a test run,
otherwise the unit is
overloaded. Fix the
cover as original.
How to handle the remote contr oller
In case using remote controller mounting to the wall, etc.
Check a signal is received correctly by pushing
button at the
position to be fixed.
Cautions for installation of the remote controller
To operate the remote controller by fixing it to the wall, etc. with a
remote controller holder, turn on the fluorescent lamp, operate the
remote controller at the position to be fixed, check the air condi-
tioner normally operates, and then mount it.
When the room temperature is sensed by the remote controller,
mount the remote controller paying attention to the following items.
Place not exposed directly to cold or hot wind.
Place not exposed directly to the sunlight.
Other places where the remote controller is not influenced.
Explanation to customers
Hand over the Owners Manual and Installation Manuals to the
customer after installation works.
Explain usage and maintenance of the remote controller according
to Owners Manual.
Lamp indication
No indication even if
the remote controller
is operated.
Cause
Power supply is not
turned on.
Miscabling between
sensor unit and indoor
unit
Defective connection
between sensor unit
and indoor unit
Miscabling or defective
connection between
indoor and outdoor
units
Protective device of
outdoor unit works.
Protective device of
indoor unit works.
Measures
Check cable
connection
and correct it.
Check
outdoor unit.
Check
indoor unit.
Self-diagnosis table and measures
Lamp indication
of sensor
: Goes off
: Flash
(0.5-sec.
interval)
Drain pipe side
of indoor unit
Refrigerant pipe
side of indoor unit
Sensor unit
installing position A
(Right side of electric
parts box)
Electric parts box
of indoor unit
Screw
Corner cap
Corner cap
Ceiling panel
Slid
Remove the thermal insulation
material, fix the cable with screws
using a clamp, and put in the
thermal insulation material again.
Connection
Connect the cables out of the sensor unit to the terminal block for
remote controller cabling of the indoor unit. (There is no polarity.)
CN001
2P White
Indoor unit Sensor unit P.C. board
Terminal block for
remote controller
cabling
White
Black
Earth
Wireless
remote controller kit
(Master)
CN1
Wired
remote controller
(Sub)
21
(Sold separately)(Sold separately)
Terminal block for
remote controller cable
Remote controller cable
(Procured locally)
(0.5 to 2mm²)
Indoor unit
21
Sensor
unit
Earth Earth Earth
(Sold
separately)
(Sold
separately)
Terminal block
for remote
controller
cable
Remote controller inter-unit
cable for group control
(Procured locally)
(0.5 to 2mm²)
21
Wired
remote controller
(Sub)
Wireless
remote controller kit
(Master)
CN1
21
Indoor unit
No.1
Indoor unit
No.2
Indoor unit
No.3
Earth
Indoor unit
No.N
Sensor
unit
NOTE :
If the room temperature data from the
remote controller is not transmitted to
the unit for 10 minutes or more, the
sensor at indoor unit side is automati-
cally selected even if the sensor at the
remote controller side is selected.
Fix the remote controller toward the
unit as possible.
S001
46
S002
3
6
2
5
1
4
Address
select
Address
S002
3
6
2
5
1
4
Address
S002
3
6
2
5
1
4
Address
S001
46
Address
select
S001
46
Address
select
Display of
remote
controller
address
Address
switch
position of
sensor
*Address switch
of sensor unit
can be set any
position.
Address Address Address Address
131313
SKN AHC
Select of operation mode
Set to A.
Select of flap indication
Set to S.
AHC
SKN
Flashes alternatively
Flashes alternatively
1
2
3
4
ON
Sensor
P.C. board
Corner cap
Cover
S 003
Bit 1 : OFF to ON
1
2
Mounting screw
Truss tapping
4 x 16
To take off remote controller,
pull it toward you.
Put on.
Push.
RESET button
Cover
Replacement of battery
1. Holding the both ends of the cover and remove it by sliding
downward.
2. Correctly insert 2 AAA alkali batteries matching + and - polarities
with indications.
3. Push SET button with something tipped and attach the cover.
Accessory parts
Requirement
The control by two remote controllers is enabled by installing the
wireless remote controller with the wired remote controller for an
indoor unit.
(Max. 2 remote controllers of wireless or wired are installable.)
2-remote controllers controlling means that one or multiple units
are operated by the multiple remote controllers.
NOTES :
1. Upon confirmation of the terminal numbers of the indoor unit,
connect the remote controller cables without miscabling.
(If applied AC 220/230/240 Volt, damage the unit.)
2. The multiple wireless remote controller kits cannot concurrently be
used for an indoor unit.
3. When installing simultaneously the wireless remote controller with
the wired remote controller, set one of them as the sub remote
controller.
When setting the wired remote controller as the sub, exchange the
address connector at the rear of P.C. board of wired remote
controller from master to sub remote controller.
When setting the wireless remote controller as the sub, turn No.3 of
DIP switch [S003] on P.C. board of wireless remote controller
sensor unit from OFF to ON.
To operate an indoor unit by 2 remote controllers
*
The indoor unit is operated if either wireless or wired remote
controller is set as master or sub remote controller.
(Total cable length: Within 400m)
Part Name
Sensor unit
Remote controller
Remote controller
holder
Q’ty
1
1
1
Part Name
Battery
Owners Manual
Tapping screw
M4 x 16mm
Clamper
Fixing screw
M4 x 12mm
Q’ty
2
1
2
1
1
How to set the fan motor speed refer to the OWNERS MANUAL
TCB-AX21U (W)-E