Balcar R410A Air Conditioner User Manual


 
26
RAV-SP1100, 1400AT-E
RAV-SM1100, 1400AT-E
Tightening of Connecting Part
(Unit: Nm)
Externally
threaded side
Internally
threaded side
Fix with spanner.
Tighten with torque wrench.
Half union or packed valve Flare nut
Flare at
indoor unit side
Flare at
outdoor unit side
Align the centers of the connecting pipes and tighten
the flare nut strong as far as possible with your
fingers.
Then fix the nut with a spanner and tighten it with
torque wrench as shown in the figure.
Cover
Cap
Piping valve
Tightened
Flare nut
Loosened
As shown in the figure, be sure to use a double
spanner to loosen or tighten the flare nut of the valve
at gas side. If using a single spanner, the nut cannot
be tightened with necessary tightening torque.
On the contrary, use a single spanner to loosen or
tighten the flare nut of the valve at liquid side.
Cover
Valve at gas side
Pressure of R410A is higher than that of R22
(Approx. 1.6 times). Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor/outdoor units at the speci-
fied tightening torque. Incomplete connections may
cause not only a gas leak, but also a trouble of the
refrigeration cycle.
Do not apply refrigerating machine oil to
the flared surface.
REQUIREMENT
1. Do not put the spanner on the cap. The valve
may be broken.
2. If applying excessive torque, the nut may be
broken according to some installation conditions.
After the installation work, be sure to check gas leak
of connecting part of the pipes with nitrogen.
Outer dia. of copper pipe
6.4 mm (diam.)
9.5 mm (diam.)
12.7 mm (diam.)
15.9 mm (diam.)
Tightening torque
14 to 18 (1.4 to 1.8 kgfm)
33 to 42 (3.3 to 4.2 kgfm)
50 to 62 (5.0 to 6.2 kgfm)
68 to 82 (6.8 to 8.2 kgfm)
4
REFRIGERANT PIPING