Balcar R410A Air Conditioner User Manual


 
125
RAV-SM561, 801CT-E
RAV-SM1101, 1401CT-E
Height of ceiling
Set the installable height of the ceiling within 4m,
otherwise the air distribution will become poor.
If height of ceiling exceeds 3.5m, hot air becomes
difficult to reach the floor surface, and then the change
of setup of high ceiling is necessary.
When incorporating a filter sold separately, the change
of setup of high ceiling is also necessary.
For the change method of high ceiling, refer to the
application control, “In case of installation to high
ceiling” and “In case of incorporating filter sold
separately” in this Manual.
List of installable ceiling height
Approx. 8m
Before installation
1. Removal of suction grille
Slide the suction grille fixing knobs (two positions)
toward the arrow direction, and then open the
suction grille.
Under the condition of suction grille opened, push
the hook section of hinges (two positions) at the
rear side, and then pull out the suction grille.
2. Removal of side panel
After removing the side panel fixing screws (1 each
at right and left), slide the side panel forward and
then remove it.
3. Removal of protective vinyl
Peel out the protective vinyl on the level flap.
4. Removal of protector
Remove the protectors (2 pcs.) of the fan.
(RAV-SM801CT only)
Suction grille
Pull out suction grille
while pushing hook.
Suction grille
fixing knob
Hinge
Slide
Slide forward.
Side panel
Level flap
Protector
Setup data
0000
0001
Standard (At shipment)
High ceiling 1
3.5m or less
4.0m or less
According to the conditions of installation, setup time
of turning-on of filter sign (notification of filter cleaning)
of the remote controller can be changed.
When it is difficult to warm up the room due to
installation place or structure of the room, the
detection temperature of heating can be raised.
For change the setup time, refer to the application
control, “Change of filter sign turning-on time” and
“How to increase the heating effect” in this Manual.
In case of wireless type
Decide the position which remote controller is
operated and the installation place.
And then refer to the Installation Manual of the
wireless remote controller kit sold separately.
(The signal of the wireless type remote controller can
be received within approx. 8m. This distance is a
criterion and varies a little according to capacity of the
battery, etc.)
To prevent malfunction, select a place where is not
affected by a fluorescent lamp or direct sunlight.
Two or more (up to 6 units) wireless-type indoor
units can be set in a room.