– 178 –
To Customers
Cautions in using the remote controller
1. After all the power supplies of the air conditioner have been turned on, turn on the power supply of the central remote
controller. (16-systems : RBC-CR1-PE, 64-systems : RBC-CR64-PE)
If the power supplies of the air conditioner and the remote controller are turned on at the same time, or if they are turned on
in reverse order, the check code [97] may be temporarily displayed on the central remote controller. When the connection
cabling and setup of the central address are correct, the connected air conditioner is displayed on the central remote
controller.
2. As described below, there are differences of the display on LCD and the individual restrictions for the operation in the handy
remote controller (RBC-AMT21E) and the central remote controller.
3. When using the remote controller with the former remote controller (RBC-AM1E, AT1E), if Last-push priority/Center/Locked
is selected on the central remote controller, the display differs on the main remote controller.
1
2
3
4
5
6
Item
Fan speed select
Fan speed select
in FAN mode
Fan speed select
in DRY mode
Air direction
adjustment
Check button
Check code
Contents
Main
remote controller
and air direction
adjustment
(No display)
Test run
(4 seconds)
Display with 3 digits
(Alphabet + 2 digits
numerals)
Central
remote controller
[LOUVER]
[LOUVER] Manual
Display of check
code and Check
reset (3 seconds)
Display with 2 digits
(Alphabet or
numerals)
Cautions
Display of air speed selection differs.
When operating the main remote controller, is not displayed.
If selecting
at the central side, is displayed on the main
remote controller.
In this time, the air speed is
.
only is displayed on the central remote controller. is
displayed on the main remote controller even by change of the
setup temperature/louver, and the air speed changes automatically.
[LOUVER] only is displayed on the central remote controller.
[LOUVER] is displayed when the flap is swinging, and ON and
OFF of the swing operation set to the louver are exchanged.
Set the air direction on the main remote controller.
In case of type without function of air direction adjustment
The function differs when the
button is pushed for a long time.
If the central remote controller-ON is reset during operation of the
air conditioner, the operation stops temporarily, and then the
operation is resumed. (Trouble of the air conditioner is cleared.)
The display of the check code differs.
Ex.) Float switch operation
Main side : [P10], Collective side : [0b]
1
2
3
Item
Last-push priority
Center
Locked
Contents
New remote
controller
(RBC-AMT21E)
(No display)
CENTER
goes on.
Former remote
controller
(RBC-AM1E, AT1E)
(No display)
CENTER
goes on.
CENTER
flashes.
Remarks
All the setups and Start/Stop operation are available.
The setup contents of the central remote controller are fixed, and
the Start/Stop operation and timer operation are available on the
main remote controller.
The setup contents of the central remote controller are fixed, and
the air conditioner stops. The operation on the main remote
controller is unavailable.
EH99774901- (EN)
* Before using the remote controller, read the Owner’s Manual thoroughly to use it correctly.
TCB-PCNT20E