Balcar R410A Air Conditioner User Manual


 
164
Test run
Before test run
Before turning on the power supply, carry out the following procedure.
1) Using 500V-megger, check 1MW or more exists between the terminal block 1 to 3 and the earth.
If 1MW or less is detected, do not run the unit. Do not apply to the remote controller circuit.
2) Check the valve of the outdoor unit being opened fully.
To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.
How to execute a test run
Using the remote controller, operate the unit as usual.
For the procedure of the operation, refer to the attached Owners Manual.
A forced test run can be executed in the following procedure if the operation stops by thermo.-OFF.
In order to prevent a serial operation, the forced test run is released after 60 minutes have passed
and returns to the usual operation.
CAUTION
When the remote controller is used for the first time, it accepts an operation approx. 5 minutes
after the power supply has been turned on.
It is not a trouble, but is because the setup of the remote controller is being checked.
For the second power-ON time and after, approx. 1 minute is required to start the operation by the
remote controller.
NOTE
Do not use the forced test run for cases
other than the test run because it applies
an excessive load to the devices.
In case of wireless remote controller
Procedure Operation contents
Turn on power of the set.
After installation, the operation is not accepted for 5 minutes when the power has been turned on
at the first time, and 1 minute when the power has been turned on at the second time and after.
Perform a test run after a specified time has passed.
Push [ ] button on the remote controller, change the operation mode to [ ] or [ ] by using [ ]
button, and then change the air speed to [
] by [ ] button.
Cooling test run
Set temperature to [18˚C] by using [ ] button.
Push [ ] button to set temperature to [19˚C] just
after confirming the receiving sound Pi.
Push [ ] button to set temperature to [18˚C] just
after confirming the receiving sound Pi.
Heating test run
Set temperature to [30˚C] by using [ ] button.
Push [ ] button to set temperature to [29˚C] just
after confirming the receiving sound Pi.
Push [ ] button to set temperature to [30˚C] just
after confirming the receiving sound Pi.
Repeat the procedure
4
5
4
5
. After approx. 10 seconds, all the display lamps [ ]
(Green), [
] (Green), and [ ] (Yellow) of the wireless sensors flash, and the operation starts.
If the lamps do not flash, repeat the procedure
2
and after.
When the test run has finished, push [ ] button to stop the operation.
<Outline of test run by using a wireless remote controller>
Cooling test run : Start/Stop 18˚C 19˚C 18˚C 19˚C 18˚C 19˚C 18˚C (Test run) Start/Stop
Heating test run : Start/Stop
30˚C 29˚C 30˚C 29˚C 30˚C 29˚C 30˚C (Test run) Start/Stop
1
2
3
4
5
6
7
ADR
Be sure to set the
air speed to [ ].
2 3, 4, 5,
6
2, 7
How to set up filter sold separately of the high ceiling
When the height of ceiling to be installed with a filter exceeds
3.5m or when installing a filter sold separately, tap-up of DC fan
is required. Tap-up of DC fan can be set at No.2 (Tap 1) and No.4
(Tap 2) of DIP switch [S003] on the wireless sensor P.C. board.
The wireless sensor P.C. board appears by removing screws at
the rear side of the wireless sensor unit and the rear cover.
Setup for high ceiling
[NOTE]
If the setup has been once performed, the set
contents of Type 1, 3, and 6 can be arbitrarily
changed. However, it is required to turn off [S003]
No.2 (Tap 1) and No.4 (Tap 2) of DIP switch and
also required to rewrite by the wired remote
controller sold separately to return the set content
to the standard one (at shipment). (For rewriting by
a wired remote controller sold separately, refer to
the Installation Manual attached to the indoor unit.)
Never set ON to DIP switch [S003] No.1 (Test
run). (A test run is carried out on the remote
controller.) (For the test run, refer to the
Installation Manual attached to the indoor unit.)
[S003] No.2 (Tap 1) and
[S003] No.4 (Tap 2) are used.
Setup for filter sold separately
Standard (At shipment)
Type 1
[S003] No.2
(Tap 1)
OFF
OFF
[S003] No.4
(Tap 2)
OFF
ON
Installable
height of ceiling
3.5m
4.0m
Standard (At shipment)
Type 1
Type 3
Type 6
[S003] No.2 (Tap 1)
OFF
OFF
ON
ON
[S003] No.4 (Tap 2)
OFF
ON
OFF
ON
Filter sold separately
Standard filter
Optical regeneration deodorant filter
High-performance filter
Deodorant filter / Ammonia deodorant filter
How to handle the remote controller
In case using remote controller mounting
to the wall, etc.
Check a signal is received correctly by
pushing
button at the position to be fixed.
Replacement of battery
1. Holding the both ends of the cover and
remove it by sliding downward.
2. Correctly insert 2 AAA alkali batteries
matching + and - polarities with indica-
tions.
3. Push SET button with something tipped
and attach the cover.
Cautions for installation of the remote controller
To operate the remote controller by fixing it to the wall,
etc. with a remote controller holder, turn on the fluores-
cent lamp, operate the remote controller at the position to
be fixed, check the air conditioner normally operates, and
then mount it.
When the room temperature is sensed by the remote
controller, mount the remote controller paying attention to
the following items.
Place not exposed directly to cold or hot wind.
Place not exposed directly to the sunlight.
Other places where the remote controller is not
influenced.
Explanation to customers
Hand over the Owners Manual and Installation
Manuals to the customer after installation works.
Explain usage and maintenance of the remote controller
according to Owners Manual.
ON
1234
2
3
4
1
2
Mounting screw
Truss tapping
4 x 16
To take off
remote controller,
pull it toward you.
Put on.
Push.
RESET button
Cover
RBC-AX22CE