AMX ViewStat Thermostat User Manual


 
Setup and Configuration
14
ViewStat Color Communicating Thermostat User Guide
Button Lockout Screen
The Button Lockout screens (FIG. 12) enable you to set locks on certain features of the thermostat so the
features cannot be changed. When you lock a feature, you also set the amount of time you want the
feature to be locked. You cannot change the features you lock using the buttons on the thermostat,
however, you can still change the locked features through AxLink. You can use the navigation buttons to
move through the highlighted options. The Mode/Select button selects the highlighted item. You can
then use the navigation buttons to change the setting of the highlighted option.
Pressing Mode/Select again highlights the next available option. The following table lists the options on
the Button Lockout screen:
User Preferences Screen Options (Cont.)
Humidity Offset The humidity offset enables you to customize the humidity shown on the
display. You can set the humidity offset in 1° increments. The default humidity
offset is 0.
Button Lockout Enables you to allow certain buttons on the thermostat to be completely or
partially disabled. Opens the Button Lockout screen. See Button Lockout
Screen section on page 14 for more information.
Config Security Code Enables you to change the security code for the thermostat. Opens the Config
Security Code screen.
Advanced Setup Opens the Advanced Setup screen.
Exit Returns you to the Settings screen.
FIG. 12
Button Lockout screens
Button Lockout Screen Options
Button Lockout Enables you to lock or unlock the buttons on the thermostat so they cannot
change certain settings. You must set this option to Lock for any lockout setting
to apply.
Temperature Lock Enables you to lock the temperature settings so they cannot be changed.
Temp Lock Time Limit Enables you to enter an amount of time in minutes in which you want the
temperature lock to last. You can set the time limit to any value between 0 and
60 minutes.
Temp Lock Range Limit Enables you to lock the temperature to a range so temperature range changes
vary by only a set number of degrees. For example, if you set the limit to 3, you
can only change the temperature by + or -3 degrees from its current setting.
You can set the range to any value between 0 and 10 degrees.
Fan Lock Enables you to lock the current fan setting so you cannot change it.
Fan Lock Time Enables you to enter an amount of time in minutes in which you want the fan
lock to last. You can set the time limit to any value between 0 and 60 minutes.