Section 2 Preparation and Installation
2-24
Series network device other than the 2194EX, the two must be
connected by an Isco RS485EX Isolator Cable (P/N 60-2004-340).
The hazardous area end, labeled with proper entity parameters,
connects to the EX Network cable.
Observe intrinsic safety requirements regarding proximity to
external sources of potential electric or magnetic interference.
Refer to IEC 10079-14 section 12.2.2.5 on installation of cables
and wiring.
If the 2150EX and AV2150EX sensor are not located in a poten-
tially explosive atmosphere, the RS485EX isolator cable can be
connected directly to the top of the 2150EX.
A site example using the Field Wizard is shown in Figure 2-2.
Figure 2-18 RS485EX Isolator Cable for Connection to a 2100 Series Network Device
To connect the EX Network and RS485EX isolator cables:
1. Remove the protective cap from the communication
connector on the top of the 2150EX module.
2. Store the protective cap in the holder next to the connector.
3. Push the 6-pin end of the EX Network cable onto the com-
munication connector on the top of the 2150EX module.
Ui = 9.282V
I i = 4.000A
Pi = 4.000W
Ci = 1.650uF
Li = 0.000uH
Safe Area End
RATED INPUT
16.6V 10A
EIA-RS485
connects to Field Wizard
or other network device
using maximum 250V
(Um = 250V)
Hazardous Area End
connects to an
EX Network Cable
(P/N 60-2004-336)
Label marking
for the RS485EX
Isolator Cable