Mitsubishi Electronics C64 Home Safety Product User Manual


 
5. Explanation of Devices
5.3 Detailed Explanation of Devices
- 67 -
5.3.6 Timer T
(1) The 100ms timer, 10ms timer and 100ms integrated timer are available for this count-up type
timer.
100ms Timer T
(a) When the input conditions are set, the count starts. When the set value is counted, that timer
contact will turn ON.
(b) If the input conditions are turned OFF, the 100ms timer count value will be set to 0, and the
contact will turn OFF.
T57 K50
X5
100ms timer
Input conditions
T57 coll OFF
T57 contact OFF
X5 OFF
ON
ON
ON
5 seconds
(c) The value is set with a decimal, and can be designated from 1 to 32767 (0.1 to 3276.7 s). The
data register (D) data can also be used as the setting value. File register (R) cannot be used.
10ms Timer T
(a) When the input conditions are set, the count starts. When the set value is counted, that timer
contact will turn ON.
(b) If the input conditions are turned OFF, the 10ms timer count value will be set to 0, and the
contact will turn OFF.
T1 K500
X5
10ms timer
Input conditions
ON
ON
ON
X5 OFF
5 seconds
T1 coll OFF
T1 contact OFF
(c) The value is set with a decimal, and can be designated from 1 to 32767 (0.01 to 327.67 s). The
data register (D) data can also be used as the setting value. File register (R) cannot be used.