7. Basic Commands
OUT (Y, M, G, L, F, B, SB, SM)
- 120 -
{ OUT (Y, M, G, L, F, B, SB, SM) ... Output (Y, M, G, L, F, B, SB, SM)
Usable device
Bit device Word device
Con-
stant
Pointer
X Y M L F BSB T SM VTCDRWSWZSDKH P
Digit
desig-
nation
Index
No. of
steps
{ { { { { {
{
{
1/2
(Note) In the modification of index, 2 steps are used for B or SB device.
Y35
M60
M61
F0
Device No.
Function
The operation results before the OUT command are output to the designated device.
OUT command
Contact
Operation
results
Coil
A contact B contact
OFF OFF Non-continuity Continuity
ON ON Continuity Non-continuity
Execution condition
This is executed per scan regardless of the operation results before the OUT command.