Carrier PC 111 Air Conditioner User Manual


 
54
Table 30 Carrier Default Program Parameter Values (Supply Fan VFD)
*These settings differ from the Toshiba defaults and are required for Carrier applications.
NOTE: To restore original factory settings, change tYP to 6 in Setup mode (SEtP). This restores the VFD original factory settings.
PARAMETER GROUP PARAMETER DEFAULT VALUE
SEtP
(Setup)
ACC1 60.0 Sec
DEC1 60.0 Sec
UL 60.0 Hz
LL 10.0 Hz*
Luln 1
P3 20%
F-P3 0.0 Hz
P4 100%
F-P4 60 Hz
tHr1 See Table 32
StC1 0
StL1 110%
OLN 1
tYP 5*
Gr.F
(Fundamental)
FH 60 Hz
Pt 2
Gr.Fb
(Feedback)
FbP1 1*
Fbln 2
GP .30
Gl 2 sec
GA 0
GFS 80
P1LL 10
PuL 1
PuUl 10
PuLL 10
Gr.SF
(Frequency Settings)
Fsor 60 Hz
Sr.n 1* (054-104 only)
SrN1 0* (054-104 only)
Gr.Pn
(Panel Control)
Fr 0*
Gr.St
(Terminal Selection)
1t 1
1t0 0
1t1 56
1t2 13
1t3 3
1t4 10
Gr.Pr
(Protection)
UuC 1*
UuCt 2
ArSt 3
Gr.Ut
(Utility)
Cnod 1*
bLSF 1* (054-104 only)
Fnod 2*
bLPn 1*