Carrier PC 111 Air Conditioner User Manual


 
32
Table 16 Quick Test, Unit Configuration and Switch Check
LEGEND
*Units are not equipped with oil pressure switches.
QUICK
TEST
STEP NO.
NORMAL
DISPLAY
DESCRIPTION CONTROL SWITCH
1. 01 Type Unit Air-Cooled VAV Configuration Header
2. 2 No. of Compressors Configuration Header
3.
2
1
No. of Unloaders
(034,038,048-088)
(044, 104)
DIP Switch No. 6 and 7
4. 60 60-Hertz Power Configuration Header
5. 0 or 1
0 No Reset (Switch Off)
1 Reset On (Switch On)
DIP Switch No. 2
6. 0 or 1
0 No Economizer (Switch Off)
1 Economizer On (Switch On)
DIP Switch No. 3
7. 0 or 1
0 No Warm-Up (Switch Off)
1 Warm-Up Used (Switch On)
DIP Switch No. 4
8. 0 or 1
0 Demand Limit Not Used
(Switch Off)
1 Demand Limit Used
(Switch On)
DIP Switch No. 5
9. 0 or 1
0 Enthalpy Switch Open
1 Enthalpy Switch Closed
EC
1.0. 1 1 Low-Pressure Switch Closed Low-Pressure Switch 1
1.1. 1 1 Low-Pressure Switch Closed Low-Pressure Switch 2
1.2. 1 No Circuit 1 Oil Pressure Switch None*
1.3. 1 No Circuit 2 Oil Pressure Switch None*
DIP
Dual, In-Line Package
EC
Enthalpy Control
VAV
Variable Air Volume