Carrier 50XJ064-104 Air Conditioner User Manual


 
7
AIR TERMINALS AND FRESH AIR DAMPER (50XJ
PCB2) The VAV Terminal Open (TRMOP), Ventilation
Output (VENTR), VAV Terminals Control (TRMCT), and
Heat Interlock Relay (HIR) terminals provide dry contacts to
command the VAV terminals open; a ventilation damper open;
VAV terminals to control to their cooling set points; and VAV
terminals to control to their heat set points, respectively.
REMOTE OCCUPANCY (ROCC) (TB2 50BV, TB6
50XJ) The 50XJ,BV unit may be commanded by a remote
control system or a twist timer to become occupied and run
when a set of dry contacts close. In order for this to occur, wire
the contacts to ROCC and C.
SMOKE DETECTOR/FIRE ALARM SHUTDOWN (FSD)
(TB2 50BV, TB6 50XJ) — To allow a smoke detector to shut
the 50XJ,BV unit down, remove the jumper from FSD to C
and wire these terminals to a set of normally closed contacts on
the smoke detector.
ALARM (ALARM) AND WARNING (WARN) OUTPUTS
(TB2 50BV, TB6 50XJ) — Two dry contacts output a dis-
crete signal when the alarm and warning lights on the display
are lit. To pick up the alarm output signal, wire between the
ALARM and ALM-CM terminals. To pick up the warning
output signal, wire between the WARN and ALM-CM
terminals.
2
3
45
61
SW1
SEN
BRN (GND)
BLU (SPT)
RED(+)
WHT(GND)
BLK(-)
CCN COM
SENSOR WIRING
Fig. 3 — Space Temperature Sensor
Typical Wiring (33ZCT55SPT)
J6
6
7
RED
BLK
RED
RED
BLK
BLK
BLK
RED
BLK
RED
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4
J6
6
7
RED
BLK
RED
BLK
SENSOR 2
SENSOR 1
RED
RED
BLK
SENSOR 3
SENSOR 4
BLK
BLK
RED
RED
RED
BLK
BLK
SENSOR 8
SENSOR 9
SENSOR 5
RED
BLK
SENSOR 6
SENSOR 7
BLK
RED
SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION
SPACE TEMPERATURE AVERAGING — 9 SENSOR APPLICATION
Fig. 4 — Space Temperature Averaging
LEGEND
Field Wiring