Carrier 50XJ064-104 Air Conditioner User Manual


 
48
Configuration Screens (cont)
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
DESCRIPTION VALUE* UNITS NAME
OMNIZONE::HIR: Heat Interlock Relay
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 5 sec DlyTim
OMNIZONE::PUMP: Pump Request
Output Logic Type Normal LogType
Minimum Off Time 5 sec MinOff
Minimum On Time 5 sec MinOn
Delay Time 5 sec DlyTim
OMNIZONE::SF: Supply Fan/VFD
Output Logic Type Normal LogType
Minimum Off Time 30 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 10 sec DlyTim
OMNIZONE::TOWER: Cooling Tower Request
Output Logic Type Normal LogType
Minimum Off Time 5 sec MinOff
Minimum On Time 5 sec MinOn
Delay Time 5 sec DlyTim
OMNIZONE::TRMCT: VAV Terminals Control
Output Logic Type Normal LogType
Minimum Off Time 60 sec MinOff
Minimum On Time 60 sec MinOn
Delay Time 5 sec DlyTim
OMNIZONE::TRMOP: VAV Terminals Open MAX
Output Logic Type Normal LogType
Minimum Off Time 5 sec MinOff
Minimum On Time 5 sec MinOn
Delay Time 5 sec DlyTim
OMNIZONE::VENTR: Ventilation Request
Output Logic Type Normal LogType
Minimum Off Time 3 sec MinOff
Minimum On Time 3 sec MinOn
Delay Time 5 sec DlyTim
OMNIZONE::WARN: Non Critical Fault
Output Logic Type Normal LogType
Minimum Off Time 4 sec MinOff
Minimum On Time 4 sec MinOn
Delay Time 10 sec DlyTim
OMNIZONE::DSALM01: Duct High Pressure
Monitored Input Point DHS Name
Comparison Point SENSDI00 Name
Alarm Inhibit Point SENSDI00 Name
Discrete Check
Alarm Logic Normal AlmLogic
Enable Delay Time 15 sec DlyTim
Persistence Time 10 sec Persist
Alarm Processor
Alarm Processing Enable AlmProc
Re-Alarm Interval 0 min ReAlmTim
Alarm=1 or Alert=0 1 Type
Alarm Level 1 AlmLevel
Alarm Source 5 AlmSrc
Alarm Routing 11010000 AlmRtg
Alarm Description Index 0 AlmDesc
Alarm Message - Part 1 Duct High Static Message
Alarm Message - Part 2 Pressure Message
Alarm Message - Part 3 Message
Alarm Message - Part 4 Message
Power on Delay 0 sec PowerUp