Carrier 50XJ064-104 Air Conditioner User Manual


 
56
Configuration Screens (cont)
*Default values from factory.
NOTE: See CC6400 Comfort Controller Overview and Configuration Manual for configuration information.
DESCRIPTION VALUE* UNITS NAME
OMNIZONE::LMALM02: Entering WaterTemp.
Monitored Input Point EWT Name
Alarm Inhibit Point SENSDI00 Name
Limit Check
Low Limit 35 dF LowLim
High Limit 95 dF HighLim
Enable Delay Time 15 sec DlyTim
Persistence Time 10 sec Persist
Hysteresis 5 ^F Hyst
Alarm Processor
Alarm Processing Enable AlmProc
Re-Alarm Interval 0 min ReAlmTim
Alarm=1 or Alert=0 1 Type
Alarm Level 1 AlmLevel
Alarm Source 5 AlmSrc
Alarm Routing 11010000 AlmRtg
Alarm Description Index 7 AlmDesc
Alarm Message - Part 1 Message
Alarm Message - Part 2 Message
Alarm Message - Part 3 Message
Alarm Message - Part 4 Message
Power on Delay 0 sec PowerUp
OMNIZONE::LMALM03: Compressor Mux
Monitored Input Point CSMUX Name
Alarm Inhibit Point SENSDI00 Name
Limit Check
Low Limit 1.5 Volts LowLim
High Limit 9.9 Volts HighLim
Enable Delay Time 15 sec DlyTim
Persistence Time 10 sec Persist
Hysteresis 0.2 Volts Hyst
Alarm Processor
Alarm Processing Enable AlmProc
Re-Alarm Interval 0 min ReAlmTim
Alarm=1 or Alert=0 1 Type
Alarm Level 1 AlmLevel
Alarm Source 5 AlmSrc
Alarm Routing 11010000 AlmRtg
Alarm Description Index 7 AlmDesc
Alarm Message - Part 1 Message
Alarm Message - Part 2 Message
Alarm Message - Part 3 Message
Alarm Message - Part 4 Message
Power on Delay 0 sec PowerUp
OMNIZONE::LMALM04: Mixed/Return Air
Monitored Input Point MA_RA Name
Alarm Inhibit Point SENSDI00 Name
Limit Check
Low Limit 35 dF LowLim
High Limit 120 dF HighLim
Enable Delay Time 10 sec DlyTim
Persistence Time 10 sec Persist
Hysteresis 5 ^F Hyst
Alarm Processor
Alarm Processing Enable AlmProc
Re-Alarm Interval 0 min ReAlmTim
Alarm=1 or Alert=0 1 Type
Alarm Level 2 AlmLevel
Alarm Source 5 AlmSrc
Alarm Routing 11010000 AlmRtg
Alarm Description Index 7 AlmDesc
Alarm Message - Part 1 Message
Alarm Message - Part 2 Message
Alarm Message - Part 3 Message
Alarm Message - Part 4 Message
Power on Delay 0 sec PowerUp