APPENDIX B — CONTROL SCREENS
Display Screens
DESCRIPTION VALUE UNITS STATUS FORCE NAME
OMNIZONE::HWP01-32:Hardware points Table 1
Supply Air Temperature 67 dF SAT
Duct Static Pressure 0.2 in H2O DSP
Comp. Status MUX 1.86 Volts CSMUX
Fire Alarm/Shut Down Enable FSD
Cond. Water Flow Switch Yes CDWF
Remote Occupancy Disable ROCC
Duct High Press. Switch Normal DHS
Entering Water Temp. 69.9 dF EWT
Compressor 1 Relay Stop CMP1
Compressor 2 Relay Stop CMP2
Compressor 3 Relay Stop CMP3
Compressor 4 Relay Stop CMP4
Supply Fan/VFD Stop SF
VFD Speed Signal 0 % SPEED
Non Critical Fault Off WARN
Critical Fault Off ALARM
Mixed/Return Air Temp 77.2 dF MA_RA
Dirty Filter Status Clean FLTS
Phase Loss Protection Normal PHASE
Ext. Supply Air Reset 0 dF RESET
Water Econ. FreezeStat Normal FREEZ
Space_Reset Sensor 79.2 dF SPT
VFD Bypass Enable Disable BYPAS
Head Pressure(Comp1) 118.76 PSIG PRES
Ventilation Request Close VENTR
VAV Terminals Control No TRMCT
2-position/Econo Valve 0 % ECONO
Reverse/Head Press Ctrl 100 % Control MVLV
Hot Water Valve 0 % HWV
Heat Interlock Relay Off HIR
Bypass Start_Stop Stop BPS_S
VAV Terminals Open MAX Close TRMOP
OMNIZONE::HWP33-64: Hardware points table 2
Cooling Tower Sump Temp. 57.5 dF TWR
Building Static Milliamp 12.51 ma BSP
Condenser Leaving Water 70.3 dF LWT
Indoor Air Quality 587.21 IAQ
Indoor Relative Humidity 49.7 % IRH
Outdoor Air Temp. 76.1 dF OAT
Heat Stage 1 Off HEAT1
Heat Stage 2 Off HEAT2
Heat Stage 3 Off HEAT3
Heat Stage 4 Off HEAT4
Pump Request Off PUMP
Cooling Tower Request Off TOWER
Exhaust Fan 0 % EXH
Ext. Dehumidification Stop DEHUM
OMNIZONE::SWP65-96:Software Points
Compressor 1 Status Off CLO1
Compressor 2 Status Off CLO2
Compressor 3 Status Off CLO3
Compressor 4 Status Off CLO4
Bypass Acc Panel Secure No BP_SAFE
DX VAV RESET Control 0 dF VAVRESET
Factory/Field Test Stop FLDTST
Building Static Pressure 0.03 in H2O BSP_IN
Time Clock Off TIMCLOCK
Cooling Disable COOLOK
Supply Fan Status Off Control SFS
Ok to run Fan No OKFAN
OK Fan + Sup. Fan Stat FALSE SF_SFS
Fan + Cond. Water Flow FALSE FAN_CDWF
Equipment Mode Cool Control MODE
Activate Evacuation Mode Disable EVAC
Space Control Point 74 dF CTRLPT
Mod. Econ Enabled No Control ECON_OK
Head Pressure Control Disable Control HEAD
Economizer Control Temp. 77.22 dF ECONPT
Compressor Cooling Disable COMPRES
Duct Static Failure Normal DSP_ALM
Compressor 1 Alarm Normal C1_ALM
Compressor 2 Alarm Normal C2_ALM
Compressor 3 Alarm Normal C3_ALM
Compressor 4 Alarm Normal C4_ALM
Cond. Flow Alarm Status Disable Control CDWF_ST