Carrier 50XJ064-104 Air Conditioner User Manual


 
10
Table 6 — Quick Access Chart
LEGEND NOTES:
1. To change from Edit mode to Status mode, press or press
again.
2. Not all available selections will have items to select in sublevels.
Automatic Run Test — The 50BV,XJ unit controls are
programmed with an automatic run test that checks connection
and operation of major components. To perform the run test:
Verify that the control display (LID device/System Monitor)
interface cable is connected to internal jack on main controller;
that the fire alarm/shutdown switch input (FSD) has a factory
jumper or field input; that Bypass (if installed) is set in the
DRIVE position; and that the Local/Off/Remote switch is set to
the REMOTE position.
NOTE: When the Local/Off/Remote switch is in the
REMOTE position, the controller time schedule is pre-set
(from the factory) as unoccupied. This means that the unit
will not turn on until the run test is enabled. However, if the
controller schedule has already been modified in the field,
and the current time of day is occupied, then the supply fan
will start. The run test will shut the fan down when it
begins. The run test will complete and then the supply will
automatically restart.
NOTE: If the Local/Off/Remote switch is in the OFF posi-
tion, it is normal for the red alarm light on the display panel
to be lit, indicating that the unit is disabled.
NOTE: If the red light stays on when the switch is moved to
REMOTE, or if any other problems occur during the run
test, refer to the Troubleshooting section of this manual.
To perform the Run Test:
1. Turn unit power on.
The LID display will show the controller identifica-
tion, time and date (Fig. 5):
OMNIZONE VPAC
hh:mm mm-dd-yy
LID
NUM.
KEY
LID FUNCTION KEYS
Algorithms
(ALGO)
Status
(STAT)
History
(HIST)
Service
(SRVC)
Alarm
(ALRM)
Setup
(SET)
Schedules
(SCHD)
1 AO—Adaptive Control Hardware Points Alarm History Function Definition Limit Set Clock Occupancy
2 AO—Cooling CV Software Points Analog Point Trace Channel Definition Setpoint Real Time Clock Setpoint
3 AO—Cooling VAV Temperature Input Discrete Point Trace System Definition Discrete Controller Password Holiday
4 AO—Fan Tracking Milliamp Input Consumable Channel Setpoint Definition First out N/A S/W Setpoint
5 AO—Heating CV Custom Milliamp Input Internal Consumable Database Control Runtime N/A Network Time
6 AO—Heating VAV Voltage Input Runtime Channel Comfort Controller # of starts N/A N/A
7 AO—Humidity Control Custom Voltage Input N/A CCN Control N/A N/A N/A
8 AO—MixedAir CVw/IAQ Sensed DiscreteInput N/A LID Preferences N/A N/A N/A
9 AO—Mixed Air VAV w/IAQ Latched Discrete Input N/A N/A N/A N/A N/A
10 AO—Permissive Interlock Pulsed Discrete Input N/A N/A N/A N/A N/A
11 AO—Reset Milliamp Output N/A N/A N/A N/A N/A
12 AO—Shared Transducer Custom Milliamp Output N/A N/A N/A N/A N/A
13 AO—Static Pressure Voltage Output N/A N/A N/A N/A N/A
14 DO—Analog Custom Voltage Output N/A N/A N/A N/A N/A
15 DO—DX-Staging VAV Discrete Output N/A N/A N/A N/A N/A
16 DO—Electric Heat CV Stepper Motor Output N/A N/A N/A N/A N/A
17 DO—Electric Heat VAV Discrete Software Point N/A N/A N/A N/A N/A
18 DO—Enthalpy Comparison Analog Software Point N/A N/A N/A N/A N/A
19 DO—Interlock Network Data Out N/A N/A N/A N/A N/A
20 DO—Lighting Control Network Data In N/A N/A N/A N/A N/A
21 DO—Permissive Interlock N/A N/A N/A N/A N/A N/A
22 DO—Pump Control N/A N/A N/A N/A N/A N/A
23 DO—Prop Thermo N/A N/A N/A N/A N/A N/A
24 DO—Prop Thermo 2 Pipe N/A N/A N/A N/A N/A N/A
25 DO—Prop Thermo 4 Pipe N/A N/A N/A N/A N/A N/A
26 DO—Staged Thermostat N/A N/A N/A N/A N/A N/A
27 DO—Staging Control N/A N/A N/A N/A N/A N/A
28 DO—Time Clock N/A N/A N/A N/A N/A N/A
29 DO—Time Clock w/Check N/A N/A N/A N/A N/A N/A
30 AOSS Schedule N/A N/A N/A N/A N/A N/A
31 Network Broadcast N/A N/A N/A N/A N/A N/A
32 Linkage/AOSS Schedule N/A N/A N/A N/A N/A N/A
33 NTFC w/Enthalpy Check N/A N/A N/A N/A N/A N/A
34 Sensor Group N/A N/A N/A N/A N/A N/A
35 WSM Air Source N/A N/A N/A N/A N/A N/A
36 WSM Cool Source N/A N/A N/A N/A N/A N/A
37 Custom Program N/A N/A N/A N/A N/A N/A
AO Analog Output
AOSS Adaptive Optimal Start/Stop
CV Constant Volume
DO Digital Output
IAQ Indoor Air Quality
N/A Not Available
NTFC Nighttime Free Cooling
VAV Variable Air Volume
WSM Water System Manager
CLEAR
EXPN/EDIT