Carrier 50XJ064-104 Air Conditioner User Manual


 
63
Maintenance Screens (cont)
DESCRIPTION VALUE UNITS STATUS FORCE NAME
OMNIZONE::LMALM01: Supply air Sensor (Typical Limit Alarm)
Monitored Input Point 66.97 dF Value
Alarm Inhibit Point Off Value
Limit Check
Alarm Status Normal Status
Alarm Value 0 dF AlmValue
Exceeded Limit 0 dF ExcdLim
Alarm Processor
Alarm Type 2AlmType
Time of Last Message 15:08 LastTime
Month of Last Message 10 LastDate
Day of Last Message 26 LastDate
Year of Last Message 1 LastDate
Task Timer 4 sec TaskTimr
OMNIZONE::DSP: Duct Static Pressure (Typical Milliamp Input)
System Value 0.2 in H2O Sysvalue
Force 0Force
Status 0 HwStat
Alarm Status Normal AlmStat
Sensor Value 0.2 in H2O SenValue
Hardware Value 4.5 ma HdwValue
Channel Number 2 ChanNum
Control Algorithm Name ANCTL01 AlgoName
Alarm Algorithm Name AlmName
OMNIZONE::ECONO: 2-position/Econo Valve (Typical Milliamp Output)
System Value 0 % Sysvalue
Force 0Force
Status 0 HwStat
Alarm Status Normal AlmStat
Control Value 0 % CtrValue
Hardware Value 4 ma HdwValue
Channel Number 27 ChanNum
Control Algorithm Name CCVAV01 AlgoName
Alarm Algorithm Name AlmName
OMNIZONE::OCCPC01: Occupancy 01
Time Schedule
Mode 0 Mode
Current Occupied Period 0 Period
Override in Progress No OverLast
Override Duration 0 min OverDura
Occupied Start Time 0:00 OccStart
Unoccupied Start Time 0:00 UnStart
Next Occupied Day NxtOccD
Next Occupied Time 0:00 NxtOccT
Next Unoccupied Day NxtUnOD
Next Unoccupied Time 0:00 NxtUnOT
Last Unoccupied Day Thu PrvUnOD
Last Unoccupied Time 15:04 PrvUnOT
Push Button Override Off Value
Thermostat Override 0 dF Value
Task Timer 1 sec TaskTimr
OMNIZONE::BYPAS: VFD Bypass Enable (Typical)
System Value Disable Sysvalue
Force 0Force
Status 0 HwStat
Alarm Status Normal AlmStat
Sensor Value Disable SenValue
Hardware Value Open HdwValue
Channel Number 23 ChanNum
Control Algorithm Name AlgoName
Alarm Algorithm Name AlmName
OMNIZONE::STPR_01: Supply Fan Speed
Analog Output Point 0 % Value
Fan Status Point Off Value
Duct Static Pressure 0 in H2O Value
Static Pressure Setpoint 0 in H2O Value
PID_Master_Loop
Reference Output 0 % RefOut
Proportional Term 0 % PTerm
Integral Term 0 % ITerm
Derivative Term 0 % DTerm
Integrator Flags 0 Flags
Task Timer 0 sec TaskTimr