Carrier 50XJ064-104 Air Conditioner User Manual


 
44
Display Screens (cont)
DESCRIPTION VALUE UNITS STATUS FORCE NAME
OMNIZONE:Custom Configuration
Compressor Stages 2 NUM_CMP
Reset Ratio 3 dF RSET_RTO
CDWF 0=NO,1=YES 0 CDFW_SWT
ECON 0=NO,1=YES 0 EWT_SNS
EWT Reset 0=NO,1=YES 1 EWT_RST
MOD.VLV 0=NO,1=YES 0 MOD_ECON
0=CONST.,1=VARIABLE 0 FLOW_TYP
0=RAT,1=MAT,2=NONE 2 MARA_SNS
PHASE 0=NO,1=YES 0 PHAS_SWT
FREEZ 0=NO,1=YES 0 FREZ_SWT
ENABLE ECON. 68 dF ECON_SET
SPT 0=NO,1=YES 0 SPT_SNS
PRES 0=NO,1=YES 0 SPT_SNS
TWR 0=NO,1=YES 0 TWR_SNS
LWT 0=NO,1=YES 0 LWT_SNS
IAQ 0=NO,1=YES 0 IAQ_SNS
IRH 0=NO,1=YES 0 IRH_SNS
BSP 0=NO,1=YES 0 BSP_SNS
BSP Range 1.00 in H2O BSP_RNG
BSP LOW VALUE -0.5 in H2O BSP_LOW
Setpoints
OMNIZONE::SETPT01: Supply fan Status
Occupied Lo Setpoint 0.3 in H2O OccLow
Occupied Hi Setpoint 0.4 in H2O OccHgh
Unoccupied Lo Setpoint 0.3 in H2O UnOccLow
Unoccupied Hi Setpoint 0.4 in H2O UnOccHgh
OMNIZONE::SETPT02: VAVRESETbaseline
Occupied Lo Setpoint 0 dF OccLow
Occupied Hi Setpoint 0 dF OccHgh
Unoccupied Lo Setpoint 0 dF UnOccLow
Unoccupied Hi Setpoint 0 dF UnOccHgh
OMNIZONE::SETPT03: Heat\Cool Mode & Reset
Occupied Lo Setpoint 70 dF OccLow
Occupied Hi Setpoint 74 dF OccHgh
Unoccupied Lo Setpoint 55 dF UnOccLow
Unoccupied Hi Setpoint 85 dF UnOccHgh
OMNIZONE::SETPT04: Head Pressure Control
Occupied Lo Setpoint 225 PSIG OccLow
Occupied Hi Setpoint 225 PSIG OccHgh
Unoccupied Lo Setpoint 225 PSIG UnOccLow
Unoccupied Hi Setpoint 225 PSIG UnOccHgh
OMNIZONE::SETPT05: Supply Static Pressure
Occupied Lo Setpoint 1.5 in H2O OccLow
Occupied Hi Setpoint 1.5 in H2O OccHgh
Unoccupied Lo Setpoint 1.5 in H2O UnOccLow
Unoccupied Hi Setpoint 1.5 in H2O UnOccHgh
OMNIZONE::SETPT06: Supply Air Temperature
Occupied Lo Setpoint 55 dF OccLow
Occupied Hi Setpoint 55 dF OccHgh
Unoccupied Lo Setpoint 55 dF UnOccLow
Unoccupied Hi Setpoint 55 dF UnOccHgh
OMNIZONE::SETPT07: Building Static Pressure
Occupied Lo Setpoint 0.02 in H2O OccLow
Occupied Hi Setpoint 0.02 in H2O OccHgh
Unoccupied Lo Setpoint 0.02 in H2O UnOccLow
Unoccupied Hi Setpoint 0.02 in H2O UnOccHgh
OMNIZONE::SETPT08: BSP raw control
Occupied Lo Setpoint 12.32 ma OccLow
Occupied Hi Setpoint 12.32 ma OccHgh
Unoccupied Lo Setpoint 12.32 ma UnOccLow
Unoccupied Hi Setpoint 12.32 ma UnOccHgh
OMNIZONE::SETPT09: Humidity Control
Occupied Lo Setpoint 0 %RH OccLow
Occupied Hi Setpoint 99 %RH OccHgh
Unoccupied Lo Setpoint 0 %RH UnOccLow
Unoccupied Hi Setpoint 99 %RH UnOccHgh