Carrier 50VQP084-300 Heat Pump User Manual


 
32
Table 12 — 50VQP300 Blower Performance Data (cont)
LEGEND
NOTES:
1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Other
speeds require field selection.
2. For applications requiring higher static pressures, contact your local Carrier repre-
sentative. Performance data does not include drive losses and is based on sea level
conditions.
3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on
lowest voltage.
4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High Rpm/
Standard Motor, E = High Rpm/Large Motor.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375
3964.8
BkW 1.41 1.48 1.56 1.71 1.86 2.00 2.15 2.30 2.38 2.45 2.60 2.75 3.88 4.08
Sheave/Mtr BBBAAAAAAACCCC——
RPM 538 574 609 640 673 703 733 761 788 812 838 863 888 912
Turns Open 5.54364.53.52.51.510210.50—
4059.2
BkW 1.41 1.56 1.71 1.86 2.00 2.15 2.30 2.38 2.45 2.60 2.75 2.90 3.05
Sheave/Mtr BBBAAAAAACCCC———
RPM 553 588 620 653 685 715 744 771 796 822 847 872 896
Turns Open 5 3.5 2.5 5.5 4 3 2.5 1.5 0.5 2.5 1.5 1 0
4153.6
BkW 1.56 1.71 1.86 2.00 2.15 2.30 2.38 2.45 2.60 2.75 2.90 3.05 3.20
Sheave/Mtr BBAAAAAAACCCC———
RPM 568 602 633 666 697 726 755 782 806 832 857 881 904
Turns Open 4.53654321021.50.50—
4248.0
BkW 1.71 1.80 1.94 2.09 2.24 2.39 2.54 2.69 2.84 2.99 3.14 3.29
Sheave/Mtr BBAAAAAACCCC————
RPM 581 613 646 678 706 735 763 791 817 842 867 889
Turns Open 4 2.5 5.5 4.5 3.5 2.5 1.5 1 2.5 2 1 0
4342.4
BkW 1.78 1.86 2.00 2.15 2.30 2.45 2.60 2.75 2.90 3.05 3.20 3.35
Sheave/Mtr BBAAAAAACCCC————
RPM 598 623 656 687 715 744 772 799 825 850 872 896
Turns Open 3.5 2.5 5 4 3 2.5 1 0.5 2 1.5 1 0
4436.8
BkW 1.86 2.00 2.15 2.30 2.45 2.60 2.75 2.90 3.05 3.20 3.35
Sheave/Mtr BAAAAAAACCC—————
RPM 605 637 666 697 727 755 783 809 835 858 882
Turns Open 3654321021.50.5
4531.2
BkW 2.00 2.15 2.30 2.45 2.60 2.75 2.90 3.05 3.20 3.35 3.50
Sheave/Mtr BAAAAAACCCC—————
RPM 618 647 678 708 738 766 793 819 844 867 891
Turns Open 2.5 5.5 4.5 3.5 2.5 1.5 0.5 2.5 1.5 1 0.5
4625.6
BkW 2.15 2.30 2.45 2.60 2.75 2.90 3.05 3.20 3.35 3.50 3.65
Sheave/Mtr AAAAAAACCCC—————
RPM 631 662 690 720 749 777 803 827 852 877 900
Turns Open 654321021.50.50—
4720.0
BkW 2.30 2.45 2.60 2.75 2.90 3.05 3.20 3.35 3.50 3.65
Sheave/Mtr AAAAAAACCC——————
RPM 642 672 702 731 760 785 811 837 862 886
Turns Open 64.53.52.52 1 0 2 10.5——————
4814.4
BkW 2.45 2.60 2.75 2.90 3.05 3.20 3.35 3.50 3.65 3.80
Sheave/Mtr AAAAAACCCE——————
RPM 655 685 714 743 769 798 822 847 872 896
Turns Open 5.5 4 3 2 1.5 0.5 2.5 1.5 0.5 0
4908.8
BkW 2.602.752.903.053.203.353.503.653.80———————
Sheave/Mtr AAAAAACCE
———————
RPM 668697726752782806832857882———————
Turns Open 5 42.52 1 0 2 10.5———————
5003.2
BkW 2.752.903.053.203.353.503.653.803.95———————
Sheave/Mtr A A A A A C C E E ———————
RPM 680709737763790817842867889———————
Turns Open 4.53.52.51.50.52.51.51 0 ———————
5097.6
BkW 2.903.053.203.353.503.653.803.954.10———————
Sheave/Mtr A A A A A C E E E———————
RPM 691717745772799825850873897———————
Turns Open 4321021.50.50———————
5192.0
BkW 3.053.203.353.503.653.803.954.10————————
Sheave/Mtr AAAAAEEE————————
RPM 704729756783810836859883————————
Turns Open 3.52.51.51 01.510.5————————
A—Standard rpm/Standard Motor
B—Low rpm/Standard Motor
bhp — Brake Horsepower
C—High rpm/Standard Motor
E—High rpm/Large Motor
ESP External Static Pressure