Carrier 50VQP084-300 Heat Pump User Manual


 
3
Table 1 — 50VQP Unit Physical Data
LEGEND
NOTES:
1. All units have grommet and spring compressor mountings, and
2.2 cm and 3.5 cm electrical knockouts.
2. Use the lowest maximum pressure rating when multiple options
are combined:
UNIT 50VQP 084 096 120 150 168 192 240 300
COMPRESSOR QUANTITY Scroll (1) Scroll (2)
Factory Charge HFC-410A (kg) per circuit 3.97 4.42 6.35 7.03 3.97 4.42 6.35 7.03
BLOWER MOTOR
Blower Motor Quantity 1
Standard Motor (kW) .75 1.12 1.49 2.24 1.49 2.24 3.73 3.73
Large Motor (kW) 1.12 1.49 2.24 3.73 2.24 3.73 5.60 5.60
BLOWER
No. of Blowers 12
Blower Wheel Size D x W (cm) 38.1 x 27.9
38.1 x
38.1
38.1 x 27.9
38.1 x
38.1
WATER CONNECTION SIZE
FPT (in.) [mm] 1-1/2 [38.1] 2 [50.8]
2-1/2
[63.5]
COAX VOLUME
Volume (liters) 8.28 9.37 13.11 18.29 24.08 27.98
CONDENSATE CONNECTION SIZE
FPT (in.) [mm] 1 [25.4]
AIR COIL DATA
Air Coil Dimensions H x W (cm) 91.4 x 121.9 91.4 x 121.9
Air Coil Total Face Area (sq m) 1.11 2.22
Air Coil Tube Size (cm) 3/8 [0.953]
Air Coil Fin Spacing (fins per cm) 5.54.725.54.72
Air Coil Number of Rows 234234
MISCELLANEOUS DATA
Filter Standard Throwaway (qty) (cm) (4) 45.74 x 63.5 x 2.5 (8) 45.74 x 63.5 x 2.5
Weight - Operating (kg) 399 422 435 725 755 769
Weight - Packaged (kg) 406 429 442 739 769 782
FPT Female Pipe Thread
OPTION MAXIMUM PRESSURE (kPa)
Base Unit 3100
Motorized Water Valve 2750
Internal Secondary Pump 999
T
Optional Discharge
Supply Air
Optional Discharge
Access
Panel
Access
Panel
Access
Panel
Access
Panel
Vibration
Pad
Control Box
Supply Air
Supply Water
Return
Water
Balancing
Valve
Valves
Trap
Condensate
24 V Remote
Mtd. Stat
Power
Supply
Disconnect
Switch or
Per Local Codes
Condensate
Water In
Water Out
Unions
Fig. 1 — Typical 50VQP Unit Installation