Carrier 50VQP084-300 Heat Pump User Manual


 
22
Table 7 — 50VQP120 Blower Performance Data
LEGEND NOTES:
1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open.
Other speeds require field selection.
2. For applications requiring higher static pressures, contact your local Carrier rep-
resentative. Performance data does not include drive losses and is based on sea
level conditions.
3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on
lowest voltage.
4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High
Rpm/Standard Motor, E = High Rpm/Large Motor.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375
1085.6
BkW 0.18 0.19 0.22 0.27 0.30 0.34 0.37 0.42 0.45 0.48 0.52 0.55 0.60 0.63
Sheave/Mtr ——BBBAAAAAACCCCC
RPM 376 423 466 503 543 580 616 649 682 712 742 770 797 822
Turns Open —64.536543215.54.5432.5
1132.8
BkW 0.19 0.22 0.27 0.30 0.34 0.37 0.42 0.45 0.52 0.52 0.57 0.60 0.67 0.70
Sheave/Mtr ——BBBAAAAACCCCCC
RPM 395 439 481 517 555 592 626 659 691 722 751 779 805 831
Turns Open 5.5 4 2.55.54.53.52.51.5 6 5.54.53.5 3 2
1180.0
BkW 0.22 0.25 0.30 0.33 0.37 0.40 0.45 0.48 0.55 0.60 0.63 0.67 0.70 0.75
Sheave/Mtr ——BBBAAAAACCCCCC
RPM 412 455 496 530 567 603 637 669 701 730 759 787 813 839
Turns Open —531.55.543216543.52.51.5
1227.2
BkW 0.220.250.300.330.370.400.450.480.550.600.630.670.700.750.78
Sheave/Mtr —BBBAAAAAACCCCCC
RPM 385 430 471 506 544 579 614 647 679 710 739 768 795 822 847
Turns Open 6 4 2.5 6 5 3.5 2.5 1.5 1 5.5 4.5 4 3 2 1.5
1274.4
BkW 0.250.300.330.370.400.450.480.550.600.630.670.700.750.780.82
Sheave/Mtr —BBBAAAAACCCCCCC
RPM 403 446 486 520 556 591 625 657 689 719 748 776 803 830 855
Turns Open 5 3.5 2 5.5 4.5 3.5 2.5 1 6 5.5 4.5 3.5 3 2 1
1321.6
BkW 0.25 0.30 0.33 0.37 0.40 0.45 0.48 0.52 0.60 0.63 0.67 0.70 0.75 0.78 0.82 0.90
Sheave/Mtr BBBAAAAAACCCCCCC
RPM 377 421 462 501 534 569 603 636 668 698 728 757 785 812 838 860
Turns Open 64.536543216543.52.51.51
1368.8
BkW 0.30 0.33 0.37 0.40 0.45 0.48 0.52 0.55 0.63 0.67 0.70 0.75 0.78 0.85 0.90 0.93
Sheave/Mtr BBBAAAAAACCCCCCC
RPM 395 438 478 515 547 582 615 647 678 708 737 765 793 819 845 868
Turns Open 5.5 4 2.5 6 4.5 3.5 2.5 1.5 1 5.5 5 4 3 2.5 1.5 0.5
1416.0
BkW 0.33 0.37 0.40 0.44 0.48 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.89 0.93 1.00
Sheave/Mtr BBBAAAAACCCCCCCC
RPM 414 453 491 529 563 595 626 659 689 717 745 774 801 826 851 877
Turns Open 4.5 3.5 2 5.5 4.5 3.5 2.5 1.5 6 5.5 4.5 3.5 3 2 1 0.5
1463.2
BkW 0.37 0.40 0.44 0.48 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.89 0.93 1.00 1.08
Sheave/Mtr BBAAAAAACCCCCCCC
RPM 431 469 504 542 575 607 637 670 699 726 754 783 809 834 859 884
Turns Open 43654321654.53.52.5210.5
1510.4
BkW 0.40 0.44 0.48 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.14
Sheave/Mtr BBAAAAAACCCCCCCC
RPM
448 485 520 556 588 619 649 680 708 736 765 791 817 841 868 891
Turns Open 3.5 2 5.54.53.52.51.5 1 5.5 5 4 3 2.51.50.5 0
1557.6
BkW 0.44 0.48 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.11 1.15
Sheave/Mtr BBAAAAACCCCCCCCC
RPM 464 500 537 570 601 631 662 691 718 745 774 799 824 849 875 898
Turns Open 31.554321.565.54.54321.50.50
1604.8
BkW 0.48 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.11 1.15
Sheave/Mtr BAAAAAACCCCCCCC—
RPM 480 515 551 583 613 642 674 701 728 754 783 808 833 857 882
Turns Open 2.5 6 4.5 3.5 3 2 1 6 5 4.5 3.5 2.5 2 1 0
1652.0
BkW 0.52 0.55 0.63 0.67 0.70 0.78 0.82 0.85 0.93 0.96 1.00 1.08 1.15 1.19 1.23
Sheave/Mtr BAAAAACCCCCCCCC—
RPM 496 530 565 596 625 654 684 711 738 766 792 816 841 867 890
Turns Open 25.543.52.51.565.54.54 32.51.51 0—
A—Standard rpm/Standard Motor
B—Low rpm/Standard Motor
bhp Brake Horsepower
C—High rpm/Standard Motor
E—High rpm/Large Motor
ESP External Static Pressure