Carrier 50VQP084-300 Heat Pump User Manual


 
14
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC (National Electrical Code) and local codes.
3. 380/420-v transformers will be connected for 380-v operation. For 420-v operation, dis-
connect VIO lead at L1, and attach BRN lead to L1. Close open end of VIO lead.
4. FP1 thermistor provides freeze protection for WATER. When using ANTIFREEZE solu-
tion, cut JW3 jumper.
5. Typical heat pump thermostat wiring shown. Refer to thermostat installation instructions
for wiring to the unit. Thermostat wiring must be “Class 1” and voltage rating equal to or
greater than unit supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut AL2 DRY (JW4) jumper and dry con-
tact will be available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws to control box.
(Ground available from top two standoffs as shown.)
8. For dual point power option, blower wires (3 qty) will go to PDB2 only.
AL Alarm Relay
BC Blower Contactor
CB Circuit Breaker
CC Compressor Contactor
CO Sensor, Condensate Overflow
DPP Dual Point Power
DS Disconnect Switch
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HP High-Pressure Switch
HPWS High-Pressure Water Switch
JW3 Clippable Field Selection Jumper
LOC Loss of Charge Pressure Switch
MV Motorized Valve
PDB Power Distribution Block
PDB2 Power Distribution Block Dual Point Option
RVS Reversing Valve Solenoid
TRANS Transformer
Factory Line Voltage Wiring
Factory Low Voltage Wiring
Field Line Voltage Wiring
Field Low Voltage Wiring
Printed Circuit Trace
Optional Wiring
LEGEND
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
Ground
Solenoid Coil
Relay Contacts - N.O.
Relay Contacts - N.C.
Temperature Switch
Switch - Low Pressure
Switch - High Pressure
Wire Nut
Fig. 28 — 50VQP084-168 with Deluxe D Control (Typical)
a50-8439
Deluxe D