Carrier 50VQP084-300 Heat Pump User Manual


 
20
Table 6 — 50VQP096 Blower Performance Data
LEGEND NOTES:
1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Other
speeds require field selection.
2. For applications requiring higher static pressures, contact your local Carrier repre-
sentative. Performance data does not include drive losses and is based on sea level
conditions.
3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on
lowest voltage.
4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High
Rpm/Standard Motor.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375
849.6
BkW 0.100.140.170.170.220.250.270.290.330.360.380.42
Sheave/Mtr —BBAAAAACCCCC———
RPM 343 395 444 488 530 568 603 636 668 697 723 751
Turns Open —53653.52.51.55432.51.5
896.8
BkW 0.110.150.180.190.230.270.280.310.350.380.410.45
Sheave/Mtr —BBAAAAACCCCC———
RPM 348 399 447 491 532 571 606 639 671 700 727 754
Turns Open 4.53653.521.55432.51.5
944.0
BkW 0.110.160.190.210.250.280.300.330.370.400.430.47
Sheave/Mtr —BBAAAAACCCCC———
RPM 352 403 450 493 534 573 608 641 673 703 730 757
Turns Open 4.535.54.5321542.521.5
991.2
BkW 0.120.180.220.250.280.310.330.370.400.440.480.52
Sheave/Mtr —BBAAAAACCCCC———
RPM 362 410 457 499 537 577 612 647 678 710 737 764
Turns Open 4 2.5 5.5 4.5 3 2 1 4.5 3.5 2.5 2 1
1038.4
BkW 0.170.210.240.250.290.330.370.400.440.480.520.55
Sheave/Mtr —BBAAAAACCCCC———
RPM 375 424 467 507 548 584 621 653 684 716 743 772
Turns Open 4 2 5 4.5 3 1.5 1 4.5 3.5 2.5 2 1
1085.6
BkW 0.16 0.18 0.22 0.25 0.29 0.33 0.37 0.40 0.44 0.48 0.52 0.55
Sheave/Mtr BBAAAAACCCCC————
RPM 339 387 435 476 518 555 590 627 659 692 721 751
Turns Open 5 3.5 6 5 4 2.5 1.5 5.5 4.5 3 2.5 1.5
1132.8
BkW 0.18 0.22 0.25 0.29 0.33 0.37 0.40 0.44 0.48 0.52 0.55 0.59
Sheave/Mtr BBAAAAACCCCC————
RPM 353 403 446 485 527 563 600 633 665 697 726 756
Turns Open 4.53653.52.51.55.54321.5
1180.0
BkW 0.21 0.23 0.25 0.29 0.33 0.37 0.40 0.44 0.48 0.55 0.59 0.63
Sheave/Mtr BBAAAAACCCCC————
RPM 362 411 452 495 532 567 604 636 670 700 729 759
Turns Open 4.02.55.54.53.52154321—
1227.2
BkW 0.22 0.25 0.32 0.36 0.40 0.43 0.47 0.51 0.55 0.58 0.62 0.66
Sheave/Mtr BBAAAAACCCCC————
RPM 377 420 460 500 536 570 606 638 671 701 729 759
Turns Open 3.525.54.53 2 1 53.52.52 1————
1274.4
BkW 0.25 0.28 0.32 0.36 0.40 0.44 0.48 0.52 0.55 0.59 0.63 0.67
Sheave/Mtr BBAAAAACCCCC————
RPM 381 423 463 504 539 576 609 641 674 703 734 762
Turns Open 3.525431.5153.52.521—
1321.6
BkW
0.25 0.29 0.33 0.37 0.40 0.48 0.52 0.55 0.59 0.63 0.67
Sheave/Mtr BBAAAAACCCC—————
RPM 390 431 474 510 545 581 613 647 677 706 737
Turns Open 325431.514.53.52.52—
1368.8
BkW 0.29 0.33 0.37 0.40 0.44 0.48 0.55 0.59 0.63 0.67 0.70
Sheave/Mtr BAAAAACCCCC—————
RPM 399 440 481 517 551 586 618 651 681 710 740
Turns Open 3 6 4.5 3.5 2.5 1.5 5.5 4.5 3 2.5 1.5
A—Standard rpm/Standard Motor
B—Low rpm/Standard Motor
bhp Brake Horsepower
C—High rpm/Standard Motor
ESP External Static Pressure