Carrier 50VQP084-300 Heat Pump User Manual


 
25
Table 8 — 50VQP150 Blower Performance Data (cont)
LEGEND NOTES:
1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open.
Other speeds require field selection.
2. For applications requiring higher static pressures, contact your local Carrier rep-
resentative. Performance data does not include drive losses and is based on sea
level conditions.
3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on
lowest voltage.
4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High
Rpm/Standard Motor, E = High Rpm/Large Motor.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375
1982.4
BkW 0.70 0.74 0.78 0.85 0.93 1.00 1.08 1.15 1.19 1.23 1.30 1.38 1.45 1.53 1.60 1.68
Sheave/Mtr BBAAAAAAACCCCCCC
RPM 538 574 609 640 673 703 733 761 788 812 838 863 888 912 934 958
Turns Open 5.54654321.515.5543.52.521.5
2029.6
BkW 0.70 0.78 0.85 0.93 1.00 1.08 1.15 1.19 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75
Sheave/Mtr BBAAAAAACCCCCCCC
RPM 553 588 620 653 685 715 744 771 796 822 847 872 896 919 942 966
Turns Open 5 3.5 5.5 4.5 3.5 2.5 2 1 6 5.5 4.5 4 3 2.5 1.5 1
2076.8
BkW 0.78 0.85 0.93 1.00 1.08 1.15 1.19 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83
Sheave/Mtr BBAAAAAACCCCCCCC
RPM 568 602 633 666 697 726 755 782 806 832 857 881 904 927 950 973
Turns Open 4.5 3 5 4 3.5 2.5 1.5 1 6 5 4.5 3.5 3 2 1.5 1
2124.0
BkW 0.85 0.90 0.97 1.05 1.12 1.20 1.27 1.35 1.42 1.50 1.57 1.65 1.72 1.80 1.87
Sheave/Mtr BAAAAAACCCCCCCC—
RPM 581 613 646 678 706 735 763 791 817 842 867 889 912 935 958
Turns Open 4 6 4.5 4 3 2 1.5 6 5.5 4.5 4 3 2.5 2 1.5
2171.2
BkW 0.89 0.93 1.00 1.08 1.15 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90
Sheave/Mtr BAAAAAACCCCCCCC—
RPM 598 623 656 687 715 744 772 799 825 850 872 896 919 942 963
Turns Open 3.5 5.5 4.5 3.5 2.5 2 1 6 5.5 4.5 3.5 3 2 1.5 1
2218.4
BkW 0.93 1.00 1.08 1.15 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97
Sheave/Mtr AAAAAAACCCCCCCC—
RPM 605 637 666 697 727 755 783 809 835 858 882 905 928 951 973
Turns Open 65432.51.515.5543.52.521.51—
2265.6
BkW 1.00 1.08 1.15 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05
Sheave/Mtr AAAAAACCCCCCCCC—
RPM 618 647 678 708 738 766 793 819 844 867 891 914 937 959 980
Turns Open 5.54.5432165.54.5432.51.51.51—
2312.8
BkW 1.08 1.15 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05 2.12
Sheave/Mtr AAAAAACCCCCCCCC—
RPM 631 662 690 720 749 777 803 827 852 877 900 923 946 966 988
Turns Open 5.5 4 3.5 2.5 1.5 1 6 5 4.5 3.5 3 2 1.5 1 1
2360.0
BkW 1.15 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05 2.12
Sheave/Mtr AAAAACCCCCCCCC——
RPM 642 672 702 731 760 785 811 837 862 886 909 932 953 975
Turns Open 54321.565.54.5432.51.511—
2407.2
BkW 1.23 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05 2.12
Sheave/Mtr AAAAACCCCCCCC———
RPM
655 685 714 743 769 798 822 847 872 896 917 940 962
Turns Open 4.5 3.5 2.5 1.5 1 6 5 4.5 3.5 3 2.5 1.5 1
2454.4
BkW 1.30 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05 2.12 2.24
Sheave/Mtr AAAACCCCCCCCE———
RPM 668 697 726 752 782 806 832 857 882 903 926 949 971
Turns Open 432.51.565.5543.52.5210—
2501.6
BkW 1.38 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05 2.12 2.20 2.31
Sheave/Mtr AAAACCCCCCCCE———
RPM 680 709 737 763 790 817 842 867 889 912 935 957 979
Turns Open 3.532165.54.54322C0—
2548.8
BkW 1.45 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05 2.12 2.20 2.31
Sheave/Mtr AAAACCCCCCCE————
RPM 691 717 745 772 799 825 850 873 897 920 943 965
Turns Open 3.5 2.5 1.5 1 5.5 5 4.5 3.5 3 2 1.5 0
2596.0
BkW 1.53 1.60 1.68 1.75 1.83 1.90 1.97 2.05 2.12 2.31 2.35 2.42
Sheave/Mtr AAACCCCCCEEE————
RPM 704 729 756 783 810 836 859 883 907 929 952 972
Turns Open 3 2 1.5 6 5.5 5 4 3.5 2.5 1 0.5 0
A—Standard rpm/Standard Motor
B—Low rpm/Standard Motor
bhp Brake Horsepower
C—High rpm/Standard Motor
E—High rpm/Large Motor
ESP External Static Pressure