Carrier 50VQP084-300 Heat Pump User Manual


 
24
Table 8 — 50VQP150 Blower Performance Data
LEGEND NOTES:
1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open.
Other speeds require field selection.
2. For applications requiring higher static pressures, contact your local Carrier rep-
resentative. Performance data does not include drive losses and is based on sea
level conditions.
3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on
lowest voltage.
4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High
Rpm/Standard Motor, E = High Rpm/Large Motor.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375
1321.6
BkW —————0.340.370.420.490.520.570.640.720.790.870.94
Sheave/Mtr —————BBAAAAAACCC
RPM —————533572606640676712746783821859901
Turns Open —————5.546543215.54.53
1368.8
BkW —————0.370.420.450.520.570.600.670.750.810.900.97
Sheave/Mtr —————BBAAAAAACCC
RPM —————544582619652686719754789823860902
Turns Open ————— 5 45.54.53.52.51.515.54 3
1416.0
BkW ————0.370.420.450.520.570.600.670.750.790.820.941.02
Sheave/Mtr ————BBBAAAAACCCC
RPM ————521558595628663697728762796828863903
Turns Open ———— 64.53.55.54.53.52.51.56 5 4 3
1463.2
BkW ————0.420.450.520.550.600.640.720.780.820.900.971.05
Sheave/Mtr ————BBAAAAAACCCC
RPM ————536572608640674705737769799832866904
Turns Open ————5.54 6543216543
1510.4
BkW ————0.450.490.550.600.670.700.750.850.900.971.051.12
Sheave/Mtr ————BBAAAAAACCCC
RPM ————548585618652685715747778807836868905
Turns Open ———— 53.55.54.53.52.51.515.553.53
1557.6
BkW 0.45 0.48 0.52 0.60 0.64 0.70 0.78 0.82 0.90 0.93 1.00 1.08 1.15
Sheave/Mtr ———BBAAAAAAACCCC
RPM 522 562 599 631 664 694 725 756 784 815 845 874 906
Turns Open ——— 64.565.54 32.51.515.54.53.53
1604.8
BkW 0.48 0.52 0.57 0.63 0.67 0.75 0.82 0.85 0.93 1.00 1.08 1.15 1.20
Sheave/Mtr ———BBAAAAAACCCCC
RPM 537 576 612 643 676 705 736 763 793 823 850 880 908
Turns Open 5.545.554321654.53.52.5
1652.0
BkW 0.52 0.57 0.60 0.67 0.75 0.78 0.85 0.93 1.00 1.05 1.12 1.20 1.23
Sheave/Mtr ———BBAAAAAACCCCC
RPM 551 589 622 655 685 716 746 776 802 829 858 886 913
Turns Open —53.55.54.53.52.52165432.5
1699.2
BkW 0.52 0.55 0.60 0.67 0.75 0.78 0.85 0.93 0.97 1.05 1.08 1.15 1.23 1.30
Sheave/Mtr ——BBAAAAAACCCCCC
RPM 526 565 600 634 665 696 727 754 783 809 837 865 891 919
Turns Open —64.5654321.565.54.5432.5
1746.4
BkW
0.55 0.63 0.67 0.70 0.78 0.85 0.93 0.97 1.00 1.08 1.15 1.23 1.30 1.38
Sheave/Mtr ——BBAAAAAACCCCCC
RPM 541 579 613 647 677 707 737 764 793 818 846 871 898 926
Turns Open 5.545.54.54321.565.54.53.532
1793.6
BkW 0.550.630.670.700.780.850.930.961.001.081.151.231.301.381.45
Sheave/Mtr —BBBAAAAAACCCCCC
RPM 519 554 591 626 659 688 718 746 774 802 829 855 879 905 931
Turns Open 6 5 3.55.54.53.52.5 2 1 5.5 5 4.53.52.5 2
1840.8
BkW 0.590.630.700.780.850.890.931.001.081.151.231.301.381.451.52
Sheave/Mtr —BBAAAAAAACCCCCC
RPM 531 569 605 639 669 702 729 757 785 811 838 862 887 913 938
Turns Open 5.5 4.5 6 5 4 3 2.5 1.5 1 5.5 5 4 3.5 2.5 2
1888.0
BkW 0.630.700.780.850.890.931.001.081.151.231.261.301.381.451.53
Sheave/Mtr —BBAAAAAACCCCCCC
RPM 545 582 618 651 683 710 739 767 794 821 845 870 895 920 945
Turns Open 5 45.54.54 3 21.565.54.54 32.52
1935.2
BkW 0.63 0.70 0.78 0.82 0.85 0.93 1.00 1.08 1.15 1.23 1.26 1.30 1.38 1.45 1.53 1.60
Sheave/Mtr BBBAAAAAACCCCCCC
RPM 523 560 596 631 661 692 722 750 778 804 831 854 879 904 928 951
Turns Open 6 4.5 3.5 5.5 4.5 3.5 2.5 1.5 1 6 5 4.5 3.5 3 2 1.5
A—Standard rpm/Standard Motor
B—Low rpm/Standard Motor
bhp Brake Horsepower
C—High rpm/Standard Motor
E—High rpm/Large Motor
ESP External Static Pressure