Carrier 50VQP084-300 Heat Pump User Manual


 
19
Table 5 — 50VQP084 Blower Performance Data
LEGEND NOTES:
1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open.
Other speeds require field selection.
2. For applications requiring higher static pressures, contact your local Carrier rep-
resentative. Performance data does not include drive losses and is based on sea
level conditions.
3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on
lowest voltage.
4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High
Rpm/Standard Motor, E = High Rpm/Large Motor.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375
755.2
BkW 0.12 0.15 0.13 0.19 0.22 0.24 0.26 0.30 0.31 0.33 0.37 0.39
Sheave/Mtr ——BBAAAACCCCCC——
RPM 388 437 482 527 564 599 630 663 690 716 744 767
Turns Open 3.5 1.5 5 3.5 2.5 1.5 5.5 4.5 3.5 2.5 2 1
802.4
BkW 0.13 0.16 0.15 0.20 0.24 0.25 0.28 0.32 0.34 0.36 0.40 0.42
Sheave/Mtr ——BBAAAACCCCCC——
RPM 392 440 485 529 566 601 633 666 693 720 747 771
Turns Open ——31.553.521.55.54.532.52 1——
849.6
BkW 0.14 0.17 0.17 0.22 0.25 0.27 0.29 0.33 0.36 0.38 0.42
Sheave/Mtr ——B B A A A A C C C C C———
RPM 395 444 488 530 568 603 636 668 697 723 751
Turns Open ——2.51 53.52 1 5 4 3 21.5———
896.8
BkW 0.15 0.18 0.19 0.23 0.27 0.28 0.31 0.35 0.38 0.41 0.45
Sheave/Mtr ——B B A A A C C C C C C———
RPM 399 447 491 532 571 606 639 671 700 727 754
Turns Open 2.5 1 4.5 3 2 5.5 5 4 3 2 1.5
944.0
BkW 0.11 0.16 0.19 0.21 0.25 0.28 0.30 0.33 0.37 0.40 0.43 0.47
Sheave/Mtr —B B A A A A C C C C C C———
RPM 352 403 450 493 534 573 608 641 673 703 730 757
Turns Open 4.5 2.5 5.5 4.5 3 2 5.5 4.5 4 2.5 2 1.5
991.2
BkW 0.12 0.18 0.22 0.25 0.28 0.31 0.33 0.37 0.40 0.44 0.48 0.52
Sheave/Mtr —B B A A A A C C C C C C———
RPM 362 410 457 499 537 577 612 647 678 710 737 764
Turns Open 4.5 2 5.5 4.5 3 1.5 5.5 4.5 3.5 2.5 1.5 1
1038.4
BkW 0.17 0.21 0.24 0.25 0.29 0.33 0.37 0.40 0.44 0.48 0.52 0.55
Sheave/Mtr —B B A A A A C C C C C C———
RPM 375 424 467 507 548 584 621 653 684 716 743 772
Turns Open —4 2 5 42.51.554.53.52.51.51 ———
1085.6
BkW 0.180.220.250.290.330.370.400.440.480.520.55————
Sheave/Mtr —B B A A A A C C C C C————
RPM —387435476518555590627659692721751————
Turns Open —3.51.55 42.51.55 4 3 21.5————
1132.8
BkW 0.180.220.250.290.330.370.400.440.480.520.550.59————
Sheave/Mtr B B B A A A A C C C C C————
RPM 353403446485527563600633665697726756————
Turns Open 4..531.54.53.52.51 5 4 3 21.5————
1180.0
BkW 0.210.230.250.290.330.370.400.440.480.550.590.63————
Sheave/Mtr B B B A A A A C C C C C————
RPM 362411452495532567604636670700729759————
Turns Open 42.514.53.52 14.54 3 2 1 ————
1227.2
BkW 0.220.250.320.360.400.430.470.510.550.580.620.66————
Sheave/Mtr B B A A A A C C C C C C————
RPM 377420460500536570606638671701729759————
Turns Open 3.525.54 3 25.54.53.52.52 1 ————
1274.4
BkW 0.250.280.320.360.400.440.480.520.550.590.630.67————
Sheave/Mtr B B A A A A C C C C C C————
RPM 381423463504539576609641674703734762————
Turns Open 3.525.54 31.55.54.53.52.51.51 ————
1321.6
BkW 0.250.290.330.370.400.480.520.550.590.630.670.70————
Sheave/Mtr B B A A A A C C C C C C————
RPM 390431474510545581613647677706737764————
Turns Open 31.553.52.51.55.543.52.51.51 ————
1368.8
BkW 0.290.330.370.400.440.480.550.590.630.670.700.78————
Sheave/Mtr B B A A A A C C C C C E————
RPM 399440481517551586618651681710740767————
Turns Open 2.51.553.52 1 5 4 3 21.51 ————
1416.0
BkW 0.320.370.400.440.480.520.550.630.670.700.780.82————
Sheave/Mtr B B A A A A C C C C E E————
RPM 412455492526563595628658687718745774————
Turns Open 2.514.53 2 1 5 4 3 21.51 ————
A—Standard rpm/Standard Motor
B—Low rpm/Standard Motor
bhp Brake Horsepower
C—High rpm/Standard Motor
E—High rpm/Large Motor
ESP External Static Pressure