Carrier 50VQP084-300 Heat Pump User Manual


 
31
Table 12 — 50VQP300 Blower Performance Data
LEGEND
NOTES:
1. Unit is factory shipped with standard static sheave and drive at 2.5 turns open. Other
speeds require field selection.
2. For applications requiring higher static pressures, contact your local Carrier repre-
sentative. Performance data does not include drive losses and is based on sea level
conditions.
3. All airflow is rated at lowest voltage. If unit is dual voltage rated, data is based on
lowest voltage.
4. A = Standard Rpm/Standard Motor, B = Low Rpm/Standard Motor, C = High Rpm/
Standard Motor, E = High Rpm/Large Motor.
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250 275 300 325 350 375
2643.2
BkW —————0.690.750.840.991.051.141.291.441.591.741.88
Sheave/Mtr —————BBBAAAAAACC
RPM —————533572606640676712746783821859901
Turns Open —————5.54 3 64.53.52 1 01.50.5
2737.6
BkW —————0.750.840.901.051.141.201.351.501.621.801.94
Sheave/Mtr —————BBBAAAAACCC
RPM —————544582619652686719754789823860902
Turns Open ————— 5 42.55.54 3 20.52.51.50
2832.0
BkW ————0.750.840.901.051.141.201.351.501.591.651.882.03
Sheave/Mtr ————BBBBAAAAACCC
RPM ————521558595628663697728762796828863903
Turns Open ———— 64.532542.51.50.5210
2926.4
BkW ————0.840.901.051.111.201.291.441.561.651.801.942.09
Sheave/Mtr ————BBBAAAAAACCC
RPM ————536572608640674705737769799832866904
Turns Open ————5.54 3 64.53.52.51.50 2 1 0
3020.8
BkW ————0.900.991.111.201.351.411.501.711.801.942.09
Sheave/Mtr ————BBBAAAAAACC—
RPM ————548585618652685715747778807836868—
Turns Open ———— 53.52.55.54321021—
3115.2
BkW 0.90 0.96 1.05 1.20 1.29 1.41 1.56 1.65 1.80 2.48 2.68 2.88
Sheave/Mtr ———BBBAAAAAACCC—
RPM 522 562 599 631 664 694 725 756 784 815 845 874
Turns Open —64.5365431.51210.5
3209.6
BkW 0.96 1.05 1.14 1.26 1.35 1.50 1.65 1.71 1.86 2.68 2.88 3.08
Sheave/Mtr ———BBBAAAAAACCC—
RPM 537 576 612 643 676 705 736 763 793 823 850 880
Turns Open 5.5 4 2.5 5.5 4.5 3.5 2.5 1.5 0.5 2 1 0.5
3304.0
BkW 1.05 1.14 1.20 1.35 1.50 1.56 1.71 1.86 2.00 2.80 3.00 3.20
Sheave/Mtr ———BBBAAAAAACCC—
RPM 551 589 622 655 685 716 746 776 802 829 858 886
Turns Open —53.525432101.510—
3398.4
BkW 1.05 1.11 1.20 1.35 1.50 1.56 1.71 1.86 1.94 2.09 2.88 3.08 3.28
Sheave/Mtr ——BBBAAAAAAACCC—
RPM 526 565 600 634 665 696 727 754 783 809 837 865 891
Turns Open —64.5365432101.510—
3492.8
BkW 1.11 1.26 1.35 1.41 1.56 1.71 1.86 1.94 2.00 2.15 3.08 3.28 3.48
Sheave/Mtr ——BBBAAAAAACCCC—
RPM 541 579 613 647 677 707 737 764 793 818 846 871 898
Turns Open
5 4 2.5 5.5 4.5 3.5 2.5 1.5 0.5 2.5 1.5 0.5 0
3587.2
BkW 1.26 1.33 1.41 1.56 1.71 1.86 1.93 2.00 2.15 2.30 3.28 3.48 3.68
Sheave/Mtr ——BBBAAAAAACCCC—
RPM 554 591 626 659 688 718 746 774 802 829 640 657 677
Turns Open —53.5254321021.50.50—
3681.6
BkW 1.181.261.411.561.711.781.862.002.152.302.453.483.68
Sheave/Mtr —BBBAAAAAAACCC——
RPM 531 569 605 639 669 702 729 757 785 811 838 645 663
Turns Open —64.53653.53210210.5
3776.0
BkW 1.261.411.561.711.781.862.002.152.302.452.533.483.68
Sheave/Mtr —BBBAAAAAACCCC——
RPM 545 582 618 651 683 710 739 767 794 821 845 651 669
Turns Open 5 4 2.5 5.5 4.5 3.5 2.5 1.5 0.5 2.5 1.5 1 0
3870.4
BkW 1.26 1.41 1.56 1.63 1.71 1.86 2.00 2.15 2.30 2.45 2.53 2.60 3.68 3.88
Sheave/Mtr BBBBAAAAAACCCC——
RPM 523 560 596 631 661 692 722 750 778 804 831 854 657 676
Turns Open 64.53.5254321021.50.50—
A—Standard rpm/Standard Motor
B—Low rpm/Standard Motor
bhp Brake Horsepower
C—High rpm/Standard Motor
E—High rpm/Large Motor
ESP External Static Pressure