Carrier 50VQP084-300 Heat Pump User Manual


 
16
Table 3 — 50VQP Unit Electrical Data — Standard Unit
LEGEND NOTES:
1. HACR circuit breaker in U.S.A. only.
2. All fuses Class RK-5.
Table 4 — 50VQP Unit Electrical Data — Dual Point Power Unit
LEGEND
NOTES:
1. HACR circuit breaker in U.S.A. only.
2. All fuses Class RK-5.
50VQP UNIT
SIZE
VOLTAGE
(V-Ph-Hz)
MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR FAN
MOTOR
FLA
TOTAL UNIT
FLA
MCA
MAX FUSE/
HACR
qty RLA LRA
084 380/420-3-50 360/440
A,B,C 1 11.2 75.0 1.8 13.0 15.8 25
E 1 11.2 75.0 2.5 13.7 16.5 25
096 380/420-3-50 360/440 A,B,C 1 12.2 101.0 2.5 14.7 17.8 25
120 380/420-3-50 360/440
A,B,C 1 16.7 111.0 3.6 20.3 24.5 40
E 1 16.7 111.0 4.9 21.6 25.8 40
150 380/420-3-50 360/440
A,B,C 1 18.6 118.0 4.9 23.5 28.2 45
E 1 18.6 118.0 7.8 26.4 31.1 45
168 380/420-3-50 360/440 A,B,C 2 11.2 75.0 3.4 25.8 28.6 35
192 380/420-3-50 360/440 A,B,C 2 12.2 101.0 4.9 29.3 32.3 40
240 380/420-3-50 360/440 A,B,C 2 16.7 111.0 7.8 41.2 45.4 60
300 380/420-3-50 360/440
A,B,C 2 18.6 118.0 7.8 45.0 49.7 60
E 2 18.6 118.0 12.2 49.4 54.0 70
FLA Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
RLA Rated Load Amps
50VQP
UNIT
SIZE
VOLTAGE
(V-Ph-Hz)
MIN/MAX
VOLTAGE
BLOWER
OPTION
COMPRESSOR EMERGENCY POWER SUPPLY
qty RLA LRA
TOTAL
COMP FLA
COMP
MCA
COMP
MAX FUSE
FAN MOTOR
FLA
FAN
MCA
FAN
MAX FUSE
084 380/420-3-50 360/440
A,B,C 1 11.2 75.0 11.2 14.0 25 1.8 2.3 15
E 1 11.2 75.0 11.2 14.0 25 2.5 3.1 15
096 380/420-3-50 360/440 A,B,C 1 12.2 101.0 12.2 15.3 25 2.5 3.1 15
120 380/420-3-50 360/440
A,B,C 1 16.7 111.0 16.7 20.9 35 3.6 4.5 15
E 1 16.7 111.0 16.7 20.9 35 4.9 6.1 15
150 380/420-3-50 360/440
A,B,C 1 18.6 118.0 18.6 23.3 40 4.9 6.1 15
E 1 18.6 118.0 18.6 23.3 40 7.8 9.8 15
168 380/420-3-50 360/440 A,B,C 2 11.2 75.0 22.4 25.2 35 3.4 4.3 15
192 380/420-3-50 360/440 A,B,C 2 12.2 101.0 24.4 27.4 35 4.9 6.1 15
240 380/420-3-50 360/440 A,B,C 2 16.7 111.0 33.4 37.6 50 7.8 9.8 15
300 380/420-3-50 360/440
A,B,C 2 18.6 118.0 37.2 41.9 60 7.8 9.8 15
E 2 18.6 118.0 37.2 41.9 60 12.2 15.3 25
FLA Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
RLA Rated Load Amps