Carrier 38AH044-084 Air Conditioner User Manual


 
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGE Hz DIAMETER — in. (mm) QUANTITY
104
208/230 60 3
5
8
(92) 2
460, 575,
380
60 3
5
8
(92) 1
346, 380/415 50 3
5
8
(92) 1
Fig. 4 Dimensions Unit 38AH104
LEGEND
C—Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH-104--- 5435 lb (2465 kg)
38AH-104--C 6160 lb (2794 kg)
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not
recommended for mounting unit to spring isolators.
4. Two 3
5
8
Љ (92-mm) dia holes are recommended for parallel conductors on
208/230 v units.
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the unit
and the isolators is recommended.
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A
and 2B for A-D corner weights.
7