DUAL CKT SINGLE CKT
SUCTION
CONNECTION(S)
2
1
⁄
8
Љ Dia [54 mm] 2
5
⁄
8
Љ Dia [67 mm]
LIQUID
CONNECTION(S)
7
⁄
8
Љ Dia [22 mm] 1
1
⁄
8
Љ Dia [29 mm]
SUCTION C 2Ј-
11
⁄
16
Љ [627mm] 1Ј-10
5
⁄
16
Љ[567mm]
LIQUID D 1Ј-10
1
⁄
16
Љ[561mm] 1Ј-10
5
⁄
16
Љ[567mm]
SUCTION (Ckt A) 1Ј-7
13
⁄
16
Љ [503mm] 2Ј-
5
⁄
8
Љ [626mm]
SUCTION (Ckt B) 2Ј-
5
⁄
8
Љ [626mm] —
LIQUID (Ckt A) 2Ј-5
3
⁄
4
Љ [756mm] 2Ј-10
5
⁄
8
Љ [879mm]
LIQUID (Ckt B) 2Ј-10
5
⁄
8
Љ [879mm] —
NOTES:
1. The approximate operating weight of the unit is:
38AH-044--- 3259 lb [1478 kg]
38AH-044--C 3547 lb [1609 kg]
38AH-054--- 3309 lb [1501 kg]
38AH-054--C 3597 lb [1632 kg]
38AH-064--- 3565 lb [1617 kg]
38AH-064--C 3998 lb [1813 kg]
2. Unit must have clearances for airflow as follows:
Top — Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mountingholes may beused to mountunit to concretepad. They arenot recommended formounting
unit to springisolators. If spring isolatorsare used, a perimetersupport channel between the unitand
the isolators is recommended.
4. One3
5
⁄
8
Љ(92mm)diameter holeisrecommendedforsingle-entrypoweronsize 064(208/230-v)units.
5. SeeTable1forriggingcenterofgravity(DimensionsX,Y).SeeTable2Aand2BforA-Dcornerweights.
6. Circled numerals in Top View refer to condenser fans by position.
Chart 1, Field Power Supply Connections
UNIT VOLTAGE Hz DIAMETER — in. [mm] QTY
044 230 50 3
5
⁄
8
[92] 1
044, 054
208/230 60 3
5
⁄
8
[92] 1
346, 380/415 50 2
1
⁄
2
[63] 1
044, 054, 064 460,575,380 60 2
1
⁄
2
[63] 1
064
208/230 60 2
1
⁄
2
[63] 2
346, 380/415 50 3
5
⁄
8
[92] 1
LEGEND
C—Copper Fin Coils
MTG — Mounting
SAE — Society ofAutomotive Engineers
Fig. 1 — Dimensions — Units 38AH044,054,064
4