Carrier 38AH044-084 Air Conditioner User Manual


 
LEGEND
AWG American Wire Gage
CR Control Relay
HD Heating Device
IFC Indoor-Fan Contactor
IFR Indoor-Fan Relay
kcmil Thousand Circular Mils
LLS Liquid Line Solenoid
NEC National Electrical Code
(U.S.A. Standard)
R—Heating Relay (field-
supplied 24-v sealed coil,
10 va maximum rating)
RV Reversing Valve
TB Terminal Block
Factory Wiring
Field Wiring
*Tocontrolheatingdeviceandprovideautomaticindoor-
fan operation on heating.
†Jumper removed only when separate 24-v trans-
formerpowersourceisusedtopowerthe33CSUCE-06
relay pack.
**Field-supplied.
NOTES:
1. LiquidlinesolenoidvalvesLLS-A1andA2areused
for solenoid drops.
2. Solenoid drop is a safety feature which prevents
refrigerant migration to the compressor during
the OFF cycle. It is recommended on all systems
and required on systems where piping exceeds
75 ft (22.9 m) in length.
3. The 33CSUCE-01 relay pack requires 10 va.
4. FactorywiringisinaccordancewithNEC;fieldmodi-
fications or additions must be in compliance with
all applicable codes.
5. Wiring for field power supply must be rated 75 C
minimum. Use copper, copper-clad aluminum, or
aluminumconductors.Maximumincomingwire size
for each terminal block is 500 kcmil.
6. Terminal blocks are for external field control con-
nections. Control connections are to be Class 1
wiring.
7. Field-supplied components (IFC, LLS-A1, and
LLS-A2) must have a maximum sealed coil rating
of 30 va each (0.25 amp at 120 vac and 0.13 amp
Fig. 21 Field Wiring, One 2-Stage Thermostat 38AH044-084 Optional Single-Circuit Units
Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.
at 230vac). Thermostatsmust have aminimum pilot
duty rating of 300 va (2.5 amps at 120 vac and
1.3 amps at 230 vac).
8. Replacement of factory wires must be with type
105 C wire or its equivalent.
9. Field-supplied liquid line solenoid valves installed at
the evaporator are required on all units.
10. Units have 175 va of power available for field-
installed accessories.
11. Tominimizevoltagedrop, thefollowingwiresizesare
recommended:
LENGTH —
Ft (M)
INSULATED WIRE — AWG
(35 C Minimum)
Up to 50
(15.2)
No. 18
50-75
(15.2-22.9)
No. 16
More Than 75
(22.9)
No. 14
29