Carrier 38AH044-084 Air Conditioner User Manual


 
*Field-supplied.
NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or
additions must be in compliance with all applicable codes.
2. Wiring for field power supply must be rated 75 C minimum. Use
copper, copper-clad aluminum, or aluminum conductors. Maxi-
mum incoming wire size for each terminal block is 500 kcmil.
3. Terminal blocks TB3 and TBX1 are for external field control con-
nections. Control connections are to be Class 1 wiring.
4. Field-suppliedcomponents(IFC,LLS-A1andA2)musthaveamaxi-
mum sealed coil rating of 30 va each (0.25 amp at 120 vac,
0.13 amp at 230 vac). AHMS IFC-AUX contact must have mini-
mum pilot duty rating of 400 va each (3.4 amps at 120 vac,
1.8 amps at 230 vac).
5. Replacement of factory wires must be with type 105 C wire or its
equivalent.
6. Field-supplied liquid line solenoid valves installed at the evapora-
tor are required on all units.
7. Units have 175 va of power available for field-installed
accessories.
LEGEND
AHMS Air Handler Motor Starter
AUX Auxilliary
C—Compressor Contactor
FU Fuse
GND Equipment Ground
IFC Indoor Fan Control
kcmil Thousand Circular Mils
LLS Liquid Line Solenoid
NEC National Electrical Code
(U.S.A. Standard)
SDR Solenoid Drop Relay
TB Terminal Block
TBX Terminal Block for Variable
Air Volume Units
TM Timer Motor
TR Timer Relay
TRAN Transformer
U—Unloader Solenoid
Factory Wiring
Field Wiring
Fig. 28 Field Wiring, Single ModuPanel™ Control, Units 38AH124 and 134
36