Carrier 38AH044-084 Air Conditioner User Manual


 
*Field-supplied.
NOTES:
1. Factory wiring is in accordance with NEC; field modifications or addi-
tions must be in compliance with all applicable codes.
2. Wiring for field power supply must be rated 75 C minimum. Use cop-
per, copper-clad aluminum, or aluminum conductors. Maximum
incoming wire size for each terminal block is 500 kcmil.
3. Terminal blocks TB3 and TB4 are for external field control connec-
tions. Control connections are to be Class 1 wiring.
4. Field-suppliedcomponents(IFC,LLS-A,andLLS-B) musthaveamaxi-
mum sealed coil rating of 30 va each (.25 amp at 120 vac, .13 amp at
230 vac). AHMS IFC-AUX must have a minimum pilot duty rating of
200 va (1.7 amps at 120 vac, 0.9 amps at 230 vac) each.
5. Replacement of factory wires must be with type 105 C wire or its
equivalent.
6. Field-suppliedliquidlinesolenoidvalves installedattheevaporator are
required on all units.
7. Units have 175 va of power available for field-installed accessories.
Fig. 24 Field Wiring, Single ModuPanel™ Control, 38AH044-084 Dual-Circuit Units
LEGEND
AHMS Air Handler Motor
Starter
AUX Auxiliary
C—Compressor Contactor
FU Fuse
GND Equipment Ground
IFC Indoor Fan Control
kcmil Thousand Circular Mils
LLS Liquid Line Solenoid
NEC National Electrical Code
(U.S.A. Standard)
SDR Solenoid Drop Relay
TB Terminal Block
TBX Terminal Block for Variable
Air Volume Units
TM Timer Motor
TR Timer Relay
TRAN Transformer
U—Unloader Solenoid
Factory Wiring
Field Wiring
32