Carrier 38AH044-084 Air Conditioner User Manual


 
*Field-Supplied.
Fig. 12 Required Location of Solenoid Valves and Recommended Filter Drier and
Sight Glass Locations for 38AH044-084 Optional Single-Circuit Units
LEGEND
A—Pipe A, Suction Riser, without Trap
B—Pipe B, Suction Riser with Trap
C—Suction Line to Condensing Unit
D—Pipe D, Suction Riser Short Lift
RED. Reducer
STR Street
NOTES:
1. Short riser, pipe D, is used when routing suction line to condens-
ing unit connection. See table at right.
2. See Tables 6A-9B for values of A, B, and C.
UNIT
38AH
PIPE D DIAMETER
Dual Circuit*
Single Circuit*
AB
in. mm in. mm in. mm
044 1
5
8
41 1
5
8
41 2
1
8
54
054 1
5
8
41 1
5
8
41 2
1
8
54
064 1
5
8
41 2
1
8
54 2
1
8
54
074 2
1
8
54 2
1
8
54 2
1
8
54
084 2
1
8
54 2
1
8
54 2
5
8
67†
094, 104 2
1
8
54 2
1
8
54
124, 134 2
5
8
67 2
5
8
67
*Maximum length of riser is 3 ft (914 mm).
†Double suction riser required if accessory unloader is field
installed.
Fig. 13 Double Suction Riser Construction
15