5-16 Operation MN1904
5.6.2 Underdamped response
If the graph shows that the response is underdamped (it overshoots the demand, as shown in
Figure 17) then the value for KDERIV should be increased to add extra damping to the move.
If the overshoot is excessive or oscillation has occurred, it may be necessary to reduce the
value of KPROP.
Measured
position
Demand
position
Figure 17 - Underdamped respons e
9. Click in the K DERIV and/or KPROP boxes and
make the required changes. The ideal
response is shown in section 5.6.4.