Toshiba HWS-1501CSHM3-E(-UK) Heat Pump User Manual


 
47
Toshiba
8-2.
Operation
Mode and
Control Method
12) Nighttime low-noise operation
A night time low-noise operation reduces operation frequency and the number of outdoor fan rotations for a certain period
during nighttime as noise control for neighborhood.
Maximum operation frequency 40.2 Hz (Hot water supply/ Heating/ Cooling)
Maximum fan tap 460 rpm (802H-E)
500 rpm (1102H-E, 1402H-E)
The nighttime low-noise operation is enabled/ disabled by changing the remote controller FC_09.
<How to set>
1)Press the TEMP. and TEST button at the same time for 4 seconds or longer. (Shifted to the nighttime low-
noise setting mode)
The Code No. field displays "09", and the DATA "0000", , and being displayed blink.
2)Press TIME to set enable "1" or disable "0".
Pressing SET change DATA and display to be lit and the setting is confirmed.
(When "1" as enable is set, the nighttime low-noise setting is enabled, the control starts at the set start time.)
3)Press TEST to exit the nighttime low-noise time setting mode. The and goes out, returning to its original
status.
Item Operation flow and applicable data, etc.
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 47 Monday, October 5, 2009 2:09 PM