Toshiba HWS-1501CSHM3-E(-UK) Heat Pump User Manual


 
107
Toshiba
Function code table
FC Item Details First shipment
01 Water heat exchanger capacity 0012: 802XWH**-E
0017: 1402XWH**-E
Depends on type
02 Cooling/Non-cooling switching 0000: Cooling 0001: No cooling 0001: No cooling
07 Hot water HP operation mode upper time limit 0000: 0 mins - 0120: 120 mins 0030: 30 mins
08 Hot Water Boost operation time 0003: 30 mins - 0018: 180 mins 0006: 60 mins
09 Hot Water Boost set temperature 0040: 40°C - 0080: 80°C 0075: 75°C
0A Anti bacteria set temperature 0070: 70°C - 0080: 80°C 0075: 75°C
0B Anti bacteria holding time 0000: 0 mins - 0060: 60 mins 0030: 30 mins
0C Mixing valve drive time 0003: 30 secs - 0024: 240 secs 0006: 60 secs
18 Upper limit of cooling set temperature 0018: 18°C - 0030: 30°C 0025: 25°C
19 Lower limit of cooling set temperature 0010: 10°C - 0018: 18°C 0010: 10°C
1A Upper limit of heating (ZONE1) set temperature 0037: 37°C - 0055: 55°C 0055: 55°C
1B Lower limit of heating (ZONE1) set temperature 0020: 20°C - 0037: 37°C 0020: 20°C
1C Upper limit of heating (ZONE2) set temperature 0037: 37°C - 0055: 55°C 0055: 55°C
1D Lower limit of heating (ZONE2) set temperature 0020: 20°C - 0037: 37°C 0020: 20°C
1E Upper limit of hot water set temperature 0060: 60°C - 0080: 80°C 0075: 75°C
1F Lower limit of hot water set temperature 0040: 40°C - 0060: 60°C 0040: 40°C
20 Hot water HP start temperature 0020: 20°C - 0045: 45°C 0038: 38°C
21 Hot water HP stop temperature 0040: 40°C - 0050: 50°C 0045: 45°C
22 Priority mode Hot water supply/Heating switching
temperature
-0020: -20°C - 0020: 20°C 0000: 0°C
23 Priority mode Boiler/Heat pump switching temperature -0020: -20°C - 0020: 20°C -0010: -10°C
24 Outside air temperature for hot water temperature
correction start
-0020: -20°C - 0010: 10°C 0000: 0°C
25 Hot water temperature correction value 0000: 0K - 0015: 15K 0003: 3K
26 Night set back change temperature range 0003: 3K - 0020: 20K 0005: 5K
27 Set temperature shift with heating Auto -0005: -5K - 0005: 5K 0000: 0K
29 Outside air temperature T1 temperature -0015: -15°C - 0000: 0°C -0010: -10°C
2B Outside air temperature T3 temperature 0000: 0°C - 0015: 15°C 0010: 10°C
2C Set temperature A with outside air temperature of -
20°C
0020: 20°C - 0055: 55°C 0040: 40°C
2D Set temperature B with outside air temperature of T1 0020: 20°C - 0055: 55°C 0035: 35°C
2E Set temperature C with outside air temperature of 0°C 0020: 20°C - 0055: 55°C 0030: 30°C
2F Set temperature D with outside air temperature of T3 0020: 20°C - 0055: 55°C 0025: 25°C
30 Set temperature E with outside air temperature of 20°C 0020: 20°C - 0055: 55°C 0020: 20°C
31 Zone2 ratio with Zone1 as Auto 0000: 0% - 0100: 100% 0080: 80°C
33 Heater control down time 0000: 5 mins
0002: 15 mins
0001: 10 mins
0003: 20 mins
0001: 10 mins
34 Heater control up time 0000: 10 mins
0002: 30 mins
0001: 20 mins
0003: 40 mins
0000: 10 mins
3A Frost protection function Yes/No 0000: No 0001: Yes 0001: Yes
3B Frost protection set temperature 0010: 10°C - 0020: 20°C 0015: 15°C
3C Water 2-way energization (logical reverse) control 0000: No 0001: Yes (Reverse) 0000: No
3E Heating HP/Boiler priority switching when using boiler 0000: Priority on HP 0001: Priority on boiler 0000: Priority on HP
+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 107 Monday, October 5, 2009 2:09 PM