Honeywell 3.5 Home Security System User Manual


 
Section 3 - Installing the Control
3-3
Installing the Keypads
Up to 31 addressable keypads (addresses 00-30)
may be used (you may need to use an auxiliary
power supply if the 750mA aux. output is
exceeded). The following keypads may be used:
2-line alpha display, 6139/6160
The length of all wire runs combined,
regardless of the wire gauge, must not
exceed 2000 feet when unshielded quad
conductor cable is used (1000 feet if
unshielded cable is run in conduit, which
acts a shield, or if shielded cable is used).
If more than one keypad is wired to one run,
then the above maximum lengths must be
divided by the number of keypads on the run
(e.g., the maximum length is 225 feet if two
keypads are wired on a #22 gauge run).
To wire the keypads, perform the following steps:
Step Action
Determine wire gauge by referring to the
Wire Run Length/Gauge table below.
Wire Run Length/Gauge Table
Wire Gauge Length
#22 gauge 450 feet
#20 gauge 700 feet
#18 gauge 1100 feet
#16 gauge 1750 feet
1
2 Wire keypads to a single wire run or connect
individual keypads to separate wire runs.
The maximum wire run length from the
control to a keypad, which is homerun back
to the control must not exceed the lengths
listed in the table.
3 Run field wiring from the control to the
keypads (using standard 4-conductor cable
of the wire gauge determined in step 1).
4 Connect the keypad(s) to terminals 6, 7, 8,
and 9 on the control board, as shown in
Figure 3-4.
KEYPADS
BLACK
RED
GREEN
YELLOW
CONTROL
TERMINALS
6
7
8
9
Figure 3-4: Keypad Connections to Control Panel
Addressing the Keypads
The keypads will not operate until they are
physically addressed and enabled in the
systems Device Programming in the #93 Menu
Mode.
Set each keypad for an individual address (00-15)
according to the keypads instructions. Set an alpha
keypad for address 00 and other keypads for higher
addresses. Any keypads set for address 02 and above
will appear blank until they are enabled in the systems
program. Each keypad must be set for a different
address.
Do not set any keypads to address 31
(nonaddressable mode). They will interfere
with other keypads (as well as other devices)
connected to the keypad terminals.
If an OC or OPEN CIRCUIT message is
present on a keypad, data from the control is
not reaching the keypad. Please check your
wiring.
Supplementary Power Supply for Additional Keypads
When the controls auxiliary power load for all devices
exceeds 750mA, you can power additional keypads from
a regulated 12VDC power supply (e.g., AD12612
(1.2A)). Use a UL Listed, battery-backed supply for UL
installations.
Connect the additional keypads as shown in Figure 3-5,
using the keypad wire colors shown. Be sure to observe
the current ratings for the power supply used.
Make connections directly to the screw
terminals as shown in Figure 3-5. Make no
connection to the keypad blue wire (if
present).
Be sure to connect the negative () terminal
on the power supply unit to terminal 7 () on
the control.
+
+
6789
SUPPLEMENTARY
POWER SUPPLY
CONTROL TERMINAL STRIP
AUX.
AUX. DATA
IN
DATA
OUT
IMPORTANT:
MAKE THESE
CONNECTIONS
DIRECTLY TO
SCREW
TERMINALS AS
SHOWN.
RED WIRE
BLACK WIRE
YELLOW WIRE
GREEN WIRE
BLACK WIRE
RED WIRE
GREEN WIRE
YELLOW WIRE
pwr_supply-002-V0
TO
MAIN
KEYPAD
TO
SECONDARY
KEYPAD
Figure 3-5: Using A Supplementary Power Supply