Item Specifications Remarks
Overload Internal electronic thermal overload relay protects drive overload.
Overvoltage Detect the excessive DC link circuit voltage to stop drive.
Overcurrent Detect overcurrent due to overload on drive output side to protect drive
Incoming surge Detect incoming surge voltage between AC power and the earth to protect
drive.
Undervoltage Detect the DC link circuit undervoltage to stop drive
Overheating
Detects the cooling fan fault or abnormal temperature rise of drive to pro-
tect drive.
Short-circuit Detect overcurrent due to short-circuit on drive output side to protect drive.
Ground fault
Detects overcorrect due to ground fault on drive output side to pro
tect drive.
(Detect at starting)
Motor protection Protect general-purpose motor with electronic thermal overload.
Input phase fail-
ure protection
(only for 3-phase
200V series)
The drive is protected against phase failure on the input side or over-current
due to inter-phase imbalance.
Stall prevention Controls frequency to prevent OC trip in case of the output current exceeds
the limit value during acceleration.
Lowers the frequency to hold almost constant torque in case of the output
current exceeds the limit value during constant speed running.
Controls frequency to prevent OU trip in case of the DC link circuit voltage
exceeds the limit value during deceleration.
Retry Retry function can be set for the protective functions OC1 to OC3 and
OU1 to OU3.(No. of times of retry: 5, waiting time: 0.5s fixed.
Dielectric
strength test
At 2000Vac for 1 min. between any main circuit terminals and
ground.(10mA or less)
Protection
Megger test At 500Vdc megger test between any main circuit terminals and ground
(5M or more)