GE AF-300 Sewing Machine User Manual


 
-
15
-
AF-300C11
4
(10 cm)
4
(10 cm)
0.4
(1 cm)
0.4
(1 cm)
2 Installation and Connection
2-1 Operating Environment
Install this product at a place satisfying the conditions listed in Table 2-1-1.
Table 2-1-1 Operating environment
Item Specifications
Place Indoor
Ambient temperature -10 to +50 °C (+14 to +122°F)
Ambient relative
humidity
5 to 95%RH(No condensation allowed)
Atmosphere
The product must not be exposed to dust, direct sunlight, corro-
sive gas, inflammable gas, oil mist, vapor, or water drops.
There must be no salt in the atmosphere.
Condensation must not be caused by sudden changes in tem-
perature.
Altitude 3300 feet (1000m) or less ( Air pressure : 86kPa to 106kPa )
Vibration
3mm: 2 to less than 9Hz
9.8 m/s
2
: 9 to less than 20Hz
2 m/s
2
: 20 to less than 55Hz
1 m/s
2
: 55 to less than 200Hz
2-2 Installation Method
¬ Tightly fasten the product in the upright position on a strong structure using four bolts (M4) with the
characters AF-300C11 facing the front. Be sure not
to turn the product upside down, and install it on a
horizontal surface.
- Heat is generated while the drive is operating, so the
gaps shown in Figure 2-2-1 are necessary for the
passage of cooling air. The generated heat is
radiated upward by the built-in cooling fan, so do not
install this product below a device that is sensitive to
heat.
® The temperature of the heat sink increases to about
90 °C while the drive is operating. Therefore, the
surface behind where the product is located must be
able to withstand this temperature increase.
!
WARNING
Install this product on a nonflammable material such as metal,
otherwise fire could occur.
¯ When installing this product in a control panel, carefully consider the ventilation to prevent the am-
bient temperature of the drive from exceeding the specified value. Do not install it in a hermetically
sealed box from which heat is not radiated fully.
0.4
(1 cm)
Figure 2-2-1 Installation direction and
surrounding space