Table 35—Fan Performance 48HJ007 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800
913 0.64 569 1010 0.80 715 1098 0.98 869 1178 1.16 1032 1252 1.35 1203
1900
952 0.73 652 1046 0.91 805 1131 1.09 965 1210 1.28 1134 1282 1.48 1311
2000
992 0.84 744 1083 1.02 903 1166 1.21 1070 1242 1.40 1245 1313 1.61 1427
2100
1032 0.95 844 1120 1.14 1010 1200 1.33 1184 1275 1.54 1365 1345 1.75 1553
2200
1073 1.07 954 1158 1.27 1127 1236 1.47 1307 1308 1.68 1495 1377 1.90 1689
2300
1114 1.21 1074 1196 1.41 1254 1272 1.62 1440 1343 1.84 1634 1409 2.07 1834
2400
1155 1.36 1204 1234 1.57 1391 1308 1.78 1584 1377 2.01 1784 1443 2.24 1990
2500
1196 1.51 1345 1273 1.73 1538 1345 1.96 1738 1412 2.19 1945 1477 2.43 2157
2600
1238 1.69 1497 1312 1.91 1697 1382 2.14 1904 1448 2.38 2117 1511 2.63 2335
2700
1280 1.87 1660 1352 2.10 1867 1420 2.34 2081 1484 2.59 2300 1546 2.84 2526
2800
1322 2.07 1835 1392 2.31 2050 1458 2.56 2270 1521 2.81 2496
2900
1364 2.28 2023 1432 2.53 2245 1496 2.78 2472
3000
1406 2.50 2224 1472 2.76 2452
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800
1322 1.56 1382 1388 1.77 1568 1451 1.98 1762 1510 2.21 1962 1568 2.44 2169
1900
1351 1.68 1495 1416 1.90 1686 1477 2.12 1885 1536 2.35 2090 1593 2.59 2302
2000
1380 1.82 1617 1444 2.04 1814 1505 2.27 2017 1563 2.51 2227 1619 2.75 2443
2100
1411 1.97 1748 1473 2.20 1950 1533 2.43 2159 1590 2.67 2374
2200
1441 2.13 1890 1503 2.36 2097 1562 2.60 2311 1618 2.85 2532
2300
1473 2.30 2041 1533 2.54 2254 1591 2.79 2474
2400
1505 2.48 2203 1564 2.73 2422
2500
1537 2.68 2376
2600
1571 2.88 2560
2700
2800
2900
3000
NOTES:
1. Grey cells indicate field-supplied d rive is required.
2. Maximum continuous bhp is2.90.
3. See general fan performance notes.
LEGEND
Bhp —Brake Horsepower
Watts — Input Watts to Motor
*Motordrive range: 1300 to1685 rpm.Allother rpmsrequire field-supplied drive.
Table 36—Accessory/FIOP EconoMi$er IV and EconoMi$er2 Static Pressure* (in. wg)
COMPONENT
CFM
1250 1500 1750 2000 2250 2500 2750 3000
Vertical EconoMi$er2and EconoMi$er IV
0.045 0.065 0.08 0.12 0.145 0.175 0.22 0.255
Horizontal EconoMi$er2 and EconoMi$erIV
0.1 0.125 0.15 0.18 0.225 0.275
LEGEND
FIOP Factory-Installed Option
*The static pressure must be added to external static pressure.The sum and the evaporator entering-air cfm should be used in conjunction with the Fan Perfor -
mance tables to determine indoor blower rpm and watts.