Carrier 48HJ004---007 Air Conditioner User Manual


 
43
Table 34—Fan Performance 48HJ007 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800
913 0.64 569 1010 0.80 715 1098 0.98 869 1178 1.16 1032 1252 1.35 1203
1900
952 0.73 652 1046 0.91 805 1131 1.09 965 1210 1.28 1134 1282 1.48 1311
2000
992 0.84 744 1083 1.02 903 1166 1.21 1070 1242 1.40 1245 1313 1.61 1427
2100
1032 0.95 844 1120 1.14 1010 1200 1.33 1184 1275 1.54 1365 1345 1.75 1553
2200
1073 1.07 954 1158 1.27 1127 1236 1.47 1307 1308 1.68 1495 1377 1.90 1689
2300
1114 1.21 1074 1196 1.41 1254 1272 1.62 1440 1343 1.84 1634 1409 2.07 1834
2400
1155 1.36 1204 1234 1.57 1391 1308 1.78 1584 1377 2.01 1784 1443 2.24 1990
2500
1196 1.51 1345 1273 1.73 1538 1345 1.96 1738 1412 2.19 1945
2600
1238 1.69 1497 1312 1.91 1697 1382 2.14 1904 1448 2.38 2117
2700
1280 1.87 1660 1352 2.10 1867 1420 2.34 2081
2800
1322 2.07 1835 1392 2.31 2050
2900
1364 2.28 2023
3000
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800
1322 1.56 1382 1388 1.77 1568 1451 1.98 1762 1510 2.21 1962
1900
1351 1.68 1495 1416 1.90 1686 1477 2.12 1885 1536 2.35 2090
2000
1380 1.82 1617 1444 2.04 1814 1505 2.27 2017
2100
1411 1.97 1748 1473 2.20 1950
2200
1441 2.13 1890 1503 2.36 2097
2300
1473 2.30 2041
2400
2500
2600
2700
2800
2900
3000
NOTES:
1. Grey cells indicate field-supplied d rive is required.
2. Maximum continuous bhp is2.40.
3. See general fan performance notes.
LEGEND
Bhp —Brake Horsepower
Watts — Input Watts to Motor
*Motordrive range: 1119 to1585 rpm.Allother rpmsrequire field-supplied drive.