Carrier 48HJ004---007 Air Conditioner User Manual


 
32
Table 14—48HJ Outdoor Sound Power (Total Unit)
UNIT
48HJ
ARI
RATING
(decibels)
OCTAVE BANDS
63 125 250 500 1000 2000 4000 8000
004,005
76 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3
006,007
80 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0
LEGEND
ARI --- Air Conditioning and Refrigeration Institute
Table 15—48HE Outdoor Sound Power (Total Unit)
UNIT
48HE
ARI
RATING
(decibels)
A--
WEIGHTED
(db)
OCTAVEBANDS
63 125 250 500 1000 2000 4000 8000
003--005 76 76 55.9 66.0 64.0 66.2 68.4 64.5 61.7 57.3
006 80 80 59.1 68.9 68.7 71.9 74.0 68.9 65.7 59.0
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils. See Table 31 and Fig. 44 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the
fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
See Tables 9 and 10 on this page for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative to verify.
4. Interpolation is permissible. Do not extrapolate.
Table 16—Fan Performance 40HE003 — Vertical Discharge Units; Standard Motor (Belt Drive)**
AIRFLOW
(Cfm)
EXTERNAL STATIC PRESSURE (in. wg)
0.1 0.2 0.4 0.6 0.8 1.0
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
Rpm Bhp
600
500 0.08 531 0.08 607 0.14 713 0.21 788 0.29
878 0.37
700
529 0.09 567 0.09 633 0.16 739 0.24 816 0.32
902 0.41
800
547 0.1 592 0.12 660 0.19 761 0.27 845 0.37
937 0.47
900
570 0.13 620 0.14 691 0.22 793 0.32 870 0.42
957 0.53
1000
599 0.15 650 0.16 717 0.26 818 0.36 894 0.47
981 0.58
48HE,HJ