Carrier 48HJ004---007 Air Conditioner User Manual


 
34
Table 19— Fan Performance 48HJ005, 48HE005 — Vertical Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bh p Watts
1200
666 0.26 257 778 0.37 367 871 0.47 471 952 0.57 572 1025 0.67 670
1300
701 0.31 306 810 0.43 426 901 0.54 540 981 0.65 651 1053 0.76 760
1400
737 0.36 361 842 0.49 491 931 0.62 616 1010 0.74 738 1081 0.86 856
1500
773 0.42 422 875 0.57 564 963 0.70 699 1040 0.84 831 1110 0.96 960
1600
810 0.49 491 909 0.65 643 994 0.79 790 1070 0.94 932 1140 1.08 1070
1700
847 0.57 567 943 0.73 730 1027 0.89 888 1101 1.05 1040 1170 1.20 1189
1800
885 0.66 652 978 0.83 826 1060 1.00 994 1133 1.16 1157
1900
923 0.75 745 1014 0.94 930 1093 1.11 1109
2000
962 0.85 847 1049 1.05 1043
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bh p Watts
1200
1093 0.77 767 1155 0.87 861 1213 0.96 955 1268 1.05 1047 1321 1.14 1137
1300
1119 0.87 866 1181 0.98 970 1239 1.08 1073 1294 1.18 1175
1400
1147 0.98 972 1208 1.09 1086
1500
1175 1.09 1086
1600
1700
1800
1900
2000
NOTES:
1. Greycells indicate field-supplied drive isrequired.
2. Maximum continuous bhp is 2.40.
3. See general fanperformancenotes.
LEGEND
Bhp— Brake H orsepower
Watts — InputWatts to Motor
*Motordrive range: 770to 1185 rpm. Allotherrpmsrequire field-supplied drive.
48HE,HJ