Carrier 48HJ004---007 Air Conditioner User Manual


 
37
Table 24—Fan Performance 48HJ007 — Vertical Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800
967 0.63 563 1075 0.80 715 1170 0.97 861 1255 1.13 1002 1333 1.28 1139
1900
1008 0.72 643 1112 0.91 805 1205 1.08 960 1289 1.25 1111 1366 1.42 1258
2000
1049 0.82 731 1151 1.02 903 1241 1.20 1068 1323 1.38 1228 1399 1.56 1384
2100
1091 0.93 827 1189 1.14 1008 1278 1.33 1183 1358 1.52 1353 1433 1.71 1519
2200
1133 1.05 933 1229 1.26 1123 1315 1.47 1308 1393 1.67 1487 1467 1.87 1662
2300
1176 1.18 1047 1268 1.40 1247 1352 1.62 1441 1429 1.84 1630 1501 2.04 1815
2400
1218 1.32 1170 1308 1.55 1380 1390 1.78 1584 1466 2.01 1782 1537 2.23 1977
2500
1261 1.47 1304 1349 1.72 1523 1429 1.96 1736 1503 2.19 1945
2600
1305 1.63 1448 1390 1.89 1677 1468 2.14 1900 1540 2.38 2117
2700
1348 1.80 1602 1431 2.07 1841 1507 2.33 2073
2800
1392 1.99 1768 1472 2.27 2016
2900
1435 2.19 1945
3000
1479 2.40 2135
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1800
1406 1.43 1273 1475 1.58 1403 1540 1.72 1531 1601 1.87 1657 1660 2.00 1780
1900
1438 1.58 1401 1505 1.73 1541 1569 1.89 1678 1630 2.04 1813 1689 2.19 1945
2000
1470 1.73 1537 1537 1.90 1686 1600 2.06 1833 1660 2.23 1977 1718 2.38 2118
2100
1502 1.89 1681 1568 2.07 1840 1631 2.25 1996
2200
1535 2.06 1834 1600 2.25 2002
2300
1569 2.25 1996
2400
2500
2600
2700
2800
2900
3000
NOTES:
1. Grey cells indicate field-supplied d rive is required.
2. Maximum continuous bhp is2.40.
3. See general fan performance notes.
LEGEND
Bhp —Brake Horsepower
Watts — Input Watts to Motor
*Motordrive range: 1119 to1585 rpm.Allother rpmsrequire field-supplied drive.
48HE,HJ