Carrier 48HJ004---007 Air Conditioner User Manual


 
41
Table 31—Fan Performance 48HJ006, 48HE006 Single-Phase — Horizontal Discharge Units;
Standard Motor (Belt Drive)*
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
0.2 0.4 0.6 0.8 1.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500
800 0.39 350 904 0.49 438 999 0.60 535 1087 0.72 640 1169 0.85 753
1600
839 0.46 412 938 0.57 505 1030 0.68 605 1115 0.80 714 1195 0.93 829
1700
879 0.54 483 974 0.65 580 1062 0.77 684 1144 0.90 796 1221 1.03 914
1800
919 0.63 561 1010 0.75 663 1095 0.87 771 1174 1.00 886 1250 1.14 1008
1900
960 0.73 648 1047 0.85 754 1129 0.98 867 1206 1.11 986 1279 1.25 1111
2000
1001 0.84 744 1085 0.96 855 1163 1.09 972 1238 1.23 1095
2100
1043 0.96 850 1123 1.09 965 1199 1.22 1086
2200
1085 1.09 966 1162 1.22 1086
2300
1127 1.23 1092
2400
2500
AIRFLOW
CFM
EXTERNAL STATIC PRESSURE (in. wg)
1.2 1.4 1.6 1.8 2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1500
1247 0.98 873 1320 1.13 1002 1390 1.28 1137
1600
1270 1.07 952 1342 1.22 1083
1700
1295 1.17 1040
1800
1321 1.28 1137
1900
2000
2100
2200
2300
2400
2500
NOTES:
1. Grey cells indicate field-supplied d rive is required.
2. Maximum continuous bhp is1.30.
3. See general fan performance notes.
LEGEND
Bhp —Brake Horsepower
Watts — Input Watts to Motor
*Motordrive range: 1035 to1460 rpm.Allother rpmsrequire field-supplied drive.
48HE,HJ