Bosch Appliances ICP-CC488 Home Security System User Manual


 
ICP-CC488 | Installation Guide | 17.0 System Event Timers EN | 78
Bosch Security Systems, Inc. | 12/08 | F01U089457-02
17.1 Programming Entry/Exit Timers
There are two programming locations for Entry
Timer 1, Entry Timer 2, Exit Time for AWAY
Mode, and Entry Guard Time for STAY Mode.
The first location of the timer allows you to set the
timer in increments of 1 sec. The sec location allows
you to set the timer in increments of 16 sec. Add
these two locations together for the total time.
Example
To set the Entry Time to 18 sec, program Location
466 as 2 (2 x 1 sec = 2 sec) and Location 467 as 1 (1
x 16 sec = 16 sec) for a total time of 18 sec (2 + 16 =
18).
17.2 Entry Timer 1
Location
466 to 467
Location Default
Increments of 1 sec
(0 sec to 15 sec)
466 4
Increments of 16 sec
(0 sec to 240 sec)
467 1
You can program Entry Timer 1 from 0 to 255 sec in
increments of 1 sec. Entry Timer 1 is the delay time
used by the Delay-1 Zones. Refer to Section 14.3.2
Zone Types on page 61 for more information.
17.3 Entry Timer 2
Location
468 to 467
Location Default
Increments of 1 sec
(0 sec to 15 sec)
468 8
Increments of 16 sec
(0 sec to 240 sec)
467 2
You can program Entry Timer 2 from 0 to 255 sec in
increments of 1 sec. Entry Timer 2 is the delay time
used by Delay-2 Zones. Refer to Section 14.3.2 Zone
Types on page 61 for more information.
17.4 Exit Timer
Location
470 to 471
Location Default
Increments of 1 sec
(0 sec to 15 sec)
470 12
Increments of 16 sec
(0 sec to 240 sec)
471 3
You can program the Exit Timer from 0 to 255 sec in
increments of 1 sec. When arming the system in
AWAY Mode, the remote codepad beeps during
Exit Time until the final 10 sec, when the codepad
sounds one continuous beep to indicate the end of
Exit Time is near.
The remote codepad always sounds one short beep
at the end of Exit Time when arming in STAY Mode
1 or STAY Mode 2.
17.5 Entry Guard Timer for STAY Mode
Location
472 to 473
Location Default
Increments of 1 sec
(0 sec to 15 sec)
472 0
Increments of 16 sec
(0 sec to 240 sec)
473 0
Entry Guard Timer for STAY Mode is the delay time
used for all zones except 24-Hour Burglary and 24-
Hour Fire Zones when the system is armed in STAY
Mode 1 or STAY Mode 2. All zones, including Delay
Zones, use this timer for the entry delay (for
example, the Entry Guard Timer overrides the delay
time programmed for a Delay Zone). If the Entry
Guard Timer is programmed as 0, each zone acts
according to its programmed zone type.
Refer to Section 14.3.7 to program zones to be
automatically isolated in STAY Mode 1. Refer to
Section 5.2.6 to program zones to be automatically
isolated in STAY Mode 2.
17.6 Delay Alarm Reporting Time
Location
474 to 475
Location Default
Increments of 1 sec (0 sec to
15 sec)
474 0
Increments of 16 sec (0 sec to
240 sec)
475 0
These locations program the time in sec that a
delayed report waits dormant in the dial buffer
before it is sent to the receiving party. If a User Code
holder resets the alarm within this time frame, the
control panel clears the dialer buffer and does not
report the alarm to the receiving party. Refer to
Section 14.3.5 Zone Options 1 on page 61 to program
zones for delay alarm reporting.
17.7 Sensor Watch Time
Location
476 to 477
Location Default
Increments of days (tens digit) 476 0
Increments of days (units digit) 477 0
The time set in these two locations determines the
number of days (0 to 99) a zone can remain sealed
before registering as a fault. This feature is active
only when the system is disarmed. If a zone
programmed for Sensor Watch is not unsealed and
reset during this time, the FAULT indicator lights.
Refer to Section 3.13 Fault Descriptions on page 18 for
more information on Sensor Watch Faults. Refer to
Section 14.3.5 Zone Options 1 on page 61 for
programming zones for Sensor Watch.